Digital OverVoltage Relay (GDR-C01) User's Manual V1.00
9 / 47
Kyongbo Electronics Co., Ltd.
1. General Features
This Relay contains Relay elements of OVR × 1, and is a Digital arithmetic relay
designed and manufactured properly for the protection against OverVoltage so it is not
just easy to change the operation time and operation voltage, but it can also record and
store fault information thereby greatly enhancing the reliability of the cable line, and the
main characteristics are as follows.
Features
Total arithmetic type OverVoltage Relay
Variety of timing characteristics : Inverse Time, Definite Time
Duration of maintaining output contact is 0.00 ~ 60.00Sec (0.01Sec Step),
and variable setting is possible
Set value and measured values are Displayed digitally through LCD Screen.
(4 x 20 LCD Screen)
Enhance reliability with surveillance function at all times
Free selection of frequency Settings according to the rated frequency of the line.
(50 / 60Hz)
Possible to set each of 5 Relay contact output (T/S Output) to 2 modes, and all
of these can be used for Alarms
- contact for Trip(1a), contact for Signal(4a)
Reliability is increased by the operation through output contacts when the Relay is
in abnormal state.
Convenient PC Application
- SetGDRSeries : change setting values, verify the measurements, verify Fault
information, display status, Remote Reset
Possible to self-test through manual Trip command(Contact Test)
Maintains thorough security using password input when changing setting values
Various communications supported
- Communication Methods : RS-232C, RS-485C (SCADA communications)
- Supported Protocol : MODBUS
Increased EMC / EMI performance
Applied Standard : Korea Electrical Manufacturers' Cooperative Standard
(KEMC1120)