EasyManua.ls Logo

KYORITSU 4116A - Page 13

KYORITSU 4116A
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Inthe event of a fault, the Fault loop impedanceshould be lowenough
(andthe Prospective Fault current higher enough) in order to havethe
automaticdisconnectionofsupplybytheinstalledprotectiondevicewithin
prescribedtimeinterval.
Everycircuitmust betested tomake surethat thefault loopimpedance
doesnotexceed thatspecified for theover currentprotectiondevice
concerned.
ForTTsystemtheFaultloopimpedanceisthesumofthefollowingpartial
impedances:
¡
Impedanceofpowertransformer'ssecondary.
¡
Phaseconductorresistancefrompowertransformertofaultlocation.
¡
Protectionconductorresistancefromfaultlocationtolocalearth
system.
¡
ResistanceoflocalearthsystemR.
¡
Resistanceofpowertransformer'searthsystemRo.
Thefigure below shows in markedline the Fault loop impedance forTT
system.
Fig.6
ForTNsystemtheFaultloopimpedanceisthesumofthefollowingpartial
impedances:
¡
Impedanceofpowertransformer'ssecondary
¡
Phaseconductorresistancefrompowertransformertofaultlocation
¡
Protectionconductorresistancefromfaultlocationtopowertransformer

Related product manuals