3.4 Applied Standards
Instrumentoperation: IEC61557-1,IEC61557-6
Safety: IEC61010-1,2-030CATⅢ(300V)-instrument
IEC61010-031CATⅢ(600V)-testlead
EMC: EN61326-1
RoHS: EN50581
Protectiondegree: IEC60529(IP54)
3.5 Features
Model5406Ahasthefollwingfeatures:
Batteryisnotused Model5406Aisnotbattery-operated,butoperates
bythevoltagesuppliedfromthesystem.
Wiringcheck Three LEDs indicate if the wiring of the circuit
undertestiscorrect.
Overtemperature Detectsoverheatingoftheinternalresistorandof
thecurrentcontrolMOSFETdisplayingawarning
symbol ( ) and automatically halting further
measurements.
Phaseangleselector The test can be selected from either the positive
(0
。
) or from the negative (180
。
) half-cycle of
voltage.Atthosetwopoints,testsminimum(best)
andmaximum(worst)triptimes.
Autodatahold Holds the displayed reading for a time after the
testiscomplete.
ULvalueselector Select UL (limit of touch voltage value) 25V or
50V. Where Uf (fault voltage) exceeds UL value,
"Uf Hi" will be displayed without starting the
measurement.
OptionalAccessory Model 7121B distribution board or lighting circuit
testlead.
protection
andUfMonitoring