3.4 Applied Standards
Instrumentoperation:  IEC61557-1,IEC61557-6
Safety:   IEC61010-1,2-030CATⅢ(300V)-instrument
  IEC61010-031CATⅢ(600V)-testlead
  EMC: EN61326-1
  RoHS: EN50581
Protectiondegree:   IEC60529(IP54)
3.5 Features
 Model5406Ahasthefollwingfeatures:
Batteryisnotused   Model5406Aisnotbattery-operated,butoperates
bythevoltagesuppliedfromthesystem.
Wiringcheck   Three LEDs indicate if the wiring of the circuit
undertestiscorrect.
Overtemperature   Detectsoverheatingoftheinternalresistorandof
thecurrentcontrolMOSFETdisplayingawarning
symbol ( ) and automatically halting further
measurements.
Phaseangleselector  The test can be selected from either the positive
(0
) or from the negative (180
) half-cycle of
voltage.Atthosetwopoints,testsminimum(best)
andmaximum(worst)triptimes.
Autodatahold   Holds the displayed reading for a time after the
testiscomplete.
ULvalueselector   Select UL (limit of touch voltage value) 25V or
50V. Where Uf (fault voltage) exceeds UL value,
"Uf Hi" will be displayed without starting the
measurement.
OptionalAccessory   Model 7121B distribution board or lighting circuit
testlead.
protection
andUfMonitoring