17
6.3. TESTING
(1)SettheTESTFUNCTION
・NOTRIPTEST..............×1/2:Maxtime1000ms
・TRIPTEST.....................×1:Maxtime1000ms
・FASTTRIPTEST..........×5:Maxtime200ms
・DCTEST........................DCTEST:Maxtime1000ms
・AUTORAMPTEST......AutoRampTEST(
)
:20%〜110% of the Rated Tripping
Current(I⊿n).
Maxtime300ms×10.
(2)PresstheTESTBUTTON
・NOTRIPTEST..............The breaker should not trip.
・TRIPTEST....................The breaker should trip.
・FASTTRIPTEST..........The breaker should trip.
・DCTEST........................The breaker should trip.
・AUTORAMPTEST.......The breaker should trip. Check Trip out
CurrentandTripoutTimeatmeasuredtrip
outcurrent.
(3)Pressthe0°/180°switchtochangethephaseandrepeatstep(2).
(4)Changethephaseagainandrepeatstep(2).
●BesuretoreturnthetestedRCDtotheoriginalconditionafterthetest.
WARNING
● Ifthevoltagebetweenphaseandearthexceedsapprox.260V,
"VL-PE"isshownontheLCDwhenthetestbuttonispressed,
andthemeasurementishalted.Disconnecttheinstrumentfrom
the mains supply and check the voltage between phase and
earthif"VL-PEHi"isindicated.
● Iftheoverheatsymbolappearsonthedisplay(
)disconnect
theinstrumentfromthemainssupplyandallowtocooldown.
● When makinga testwith therange largerthan theRCD rated
trippingcurrentorwhenwiringisnotcorrect,itcanhappenthat
RCDtripsand"no"isshownonthedisplay.
● When the Uf voltage rises to UL value or greater, the
measurement is automatically suspended and "Uf Hi" is
displayedontheLCD.
MAKE SURE TO KEEP CLEAR OF EARTHED METAL DURING THE
OPERATIONOFTHESETESTS.