There is also another kind of RCD called "Type B", for which tripping is
ensured for residual sinusoidal alternating currents (like type AC) and
residual pulsating DC currents (like type A) and pure or nearly pure DC
current,whethersuddenlyappliedorslowlyrising.Itisalsoveryrarelyused
inpracticebecausetheseareonlyafewmodelsonthemarketandtheprice
atthemomentisveryhigh.
Tripping current I⊿ is the lowest residual current which can still cause
trippingoutRCD.
TheRCDtesterModel5406Astartstodrive test current from 20% of I⊿n
andthenincreasesituntilRCDtripsorupto110%ofI⊿n.
ThistestisnormallynamedAutoramptestanditcanbeusedtoconfirmthe
realsensibilityoftheRCD.
IfRCDtripsbeforethe50%ofitsI⊿n,therecouldbeacertainleakageor
faultcurrentthatisalreadyflowingtotheground,ortheRCDcouldbeoutof
characteristics.
In order to check the leakage or fault currents there are specific leakage
clampmetersasModel2432,Model2433,Model2413F.
TheRCDtesterModel5406AcantesttheTripouttimet⊿andtheTripping
currentI⊿.