6 Operation
6.1.7 Calling the Checksums
1
st
safety time oil in seconds
2
nd
safety time oil in seconds
1
st
safety time gas in seconds
2
nd
safety time gas in seconds
pre-purge time in seconds
In the ETAMATIC without pilot burner, the 2
nd
safety time includes the safety time. The 1
st
safety time figure is then irrelevant.
If you have changed parameters, reset the ETAMATIC. Only a reset refreshes a checksum.
Press keys 16 and 17 to select "setpoint feedback”.
Press key 11 ENTER.
The following values are displayed one by one:
CRC 16 of the levels 0, 1 and 2: adjustable at commissioning time
4: adjustable by LAMTEC only
Press key 11 ENTER again.