EasyManua.ls Logo

Lamtec ETAMATIC - 2 Safety; 2.1 Safety Information and Symbols

Lamtec ETAMATIC
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
6 Operation
6 Operation
6.1 CO/O
2
Control
6.1.1 What happens if a fault occurs in the O
2
trim?
A warning is indicated in case of a fault and the O
2
trim is switched off. The preset values are
set anew. The burner would not shut-down automatically.
1 Fault message is displayed (O
2
controller faulty).
2 Explaination text is displayed (e.g. O
2
measuring value faulty).
3 Settings of preset basic value without control e.g. for air deficiency.
4 Display of running text (O
2
trim faulty)
NOTICE
The display texts are shown every 10 - 15 s alternately. Therefore a keypress to call the ex-
planation text is not necessary.
6.1.2 Resetting O
2
Errors
Each new burner start-up resets O
2
fault automatically. This is permissible, because a 100%
O
2
measurement test is performed at each start-up.
Manual resetting of O
2
fault is possible at any time, as follows:
Press key RESET
ETAMATIC in O
2
trim mode
If not, switch over to O
2
trim mode
Press key 15 M once
Press key ENTER and call up the cause of fault (mandatory!)
Press key 7

Other manuals for Lamtec ETAMATIC

Related product manuals