3 Product Description
3 Product Description
3.1 Design and Accessory LS2 Lambda Probe
The Lambda Probe LS2 provide the in situ (direct in the flue gas) measurement of O
2
concen-
tration in exhaust gases in the super-stoichiometric range (>1).
Fig. 3-1 Lambda Probe LS2 standard design
Alternatively:
Fig. 3-2 Lambda Probe LS2 in HT design
1 Lambda Probe LS2 in standard housing up to 300 °C (572 °F)
Default cable length is 2 m (6.5 ft), FEP, with connecting plug
2 Probe installation fitting (PIF)
3 Gas Extraction Device (GED)
1 Lambda Probe LS2-HT with flue gas bypass tube, temperature up to 1200 °C
(2192 °F) depending on material,
750 °C (1382 °F) Stainless steel
950 °C (1742 °F) Inconel
1200 °C (2192 °F) Kanthal
Temperature at probe heat max.100 °C (212 °F)
Default cable length is 2 m (6.5 ft), FEP, with connecting plug
2 Flue gas bypass tube