3 101 70 3 101 71 3 101 72
General characteristics
Nominal power (VA) 1000 2000 3000
Active Power (W) 900 1800 2700
Technology on-line, double conversion, VFI-SS-111
Waveform sinusoidal
Bypass
internal automatic bypass
external maintenance bypass (optional)
Input characteristics
Connection
10 A,
IEC 320-C14
10 A,
IEC 320-C14
16 A,
IEC 320-C20
Rated voltage 230 V
Range of voltage from 160 V to 288 V at full load
Rated frequency 50 / 60 Hz ± 5 %
Maximum current 6,8 A 13,6 A 20,0 A
Total harmonic distortion of
the current
THDi < 7% at full linear load and normal voltage
Power factor ≥ 0.99 (with full linear load)
Number of phases Single phase
Output characteristics
Outlets
(6) 10 A,
IEC 320-C13
(6) 10 A,
IEC 320-C13
(6) 10A,
IEC 320-C13
+
(1) 16A
IEC 320-C19
Rated voltage
230 V ± 1%
adjustable to 200/208/220/230/240 V
Rated frequency 50 / 60 Hz ± 0,1%
Crest factor 3:1
Total harmonic distortion of
the voltage
< 3% at full linear load
< 7% at full non-linear load
Eciency up to 90% up to 91% up to 92%
Overload capacity
105% continuous
120% for 30 seconds
150% for 10 seconds
Number of phases Single phase
Batteries and battery charger characteristics
Number of batteries 3 6 6
Battery type Lead-acid sealed without maintenance (VRLA)
Unitary capacity 12 Vdc - 7.2 Ah 12 Vdc - 7.2 Ah 12 Vdc - 9 Ah
7 Technical specifications