20
Figure.6.2-5
Remove the side parts which xes the carrier wooden
bar to the pallet. Unload the UPS from the pallet.
Fix the UPS to the ground as shown in the picture.
It is recommended to store the original UPS packaging for future needs.
The equipment may only be installed and commissioned by authorized LEGRAND
UPS Technical Service Sta or authorized LEGRAND distributor Technical Service
Sta.
When the UPS is brought from a cold place to a warmer place, humidity of the air may
condensate in it. In this case, wait minimum for 2 (two) hours before powering the UPS.
KEOR T EVO must be protected from voltage surge with devices that are suited to the installation;
the mains voltage surge must be limited to 2kV. These protective devices must be sized to take
into account all the installation parameters (geographical position whether or not there is a
lightning rod, whether or not there are other suppressors in the electrical installation, etc )
Do not connect the output neutral to the protective ground or protective bonding
Power cables and communication cables shall be installed on trays according to the
standards of the country.