Trimod HE
User manual
39
SCREEN DISPLAYED ON STARTUP OR SHUT DOWN
MESSAGE MEANING AND OPERATING ADVICE
First Turn ON: Supply Mains!
The UPS has never been turned on. No mains input. Start-up not permitted.
Make sure the mains is present before turning on.
Mains not Present!
Start-up not Allowed
No mains input. Start-up not permitted. To start the UPS in stored energy
mode select this conguration from the control panel (paragraph 5.4.2).
Emergency Power Off!
The Emergency Power O (EPO) has been activated. The EPO command has
been sent by a push-button or a switch on the input line has been opened
during the normal functioning of the UPS. Check the emergency push-button.
Incomplete Setup
for start-up!
The UPS requires a complete conguration for start-up.
Check that the output conguration, bypass enabling, number of KB, number
of batteries per KB and output voltage have been inserted properly.
Three Phase Voltage
Sequence Invalid!
The three phase sequence is not valid. A skilled technician must check that the
input three phase system has been correctly connected.
Invalid PM SW Versions:
to execute update
The SW versions of some or of all the power modules are not correct. Press the
ENTER key to update. At the end of the update, the UPS continues the start-up
procedure.
Invalid PM HW Versions!
One or more power modules are not compatible with the UPS.
Contact the LEGRAND Technical Support Service.
STARTUP Error!
An error has occurred during the start-up procedure of the UPS.
Contact the LEGRAND Technical Support Service.
Start-up aborted
The start-up has not been conrmed from the control panel within 30 seconds
of the conrmation request of the start-up procedure.
UPS turned off by program! UPS shut down as programmed via software in a remote controlled system
Incorrect setup turn-off
An error has occurred during the conguration. UPS is shutting down.
One or more of the parameters have not been set properly. Check the congu-
ration from the control panel.
Incorrect KB setup turn-off
An error has occurred during the conguration of the number of KB.
Set the right number of KB from the control panel (paragraph 5.4.2)
Low Battery TurnOff
UPS shutdown during battery mode because the minimum voltage level of the
batteries has been reached
Battery Start up Failed.
Check polarity.
The batteries are not connected to the UPS or the BUS is not properly charged.
A skilled technician must verify the batteries.
Battery Time Expired
UPS shutdown during battery mode because the maximum battery operating
time set from the control panel has been reached (paragraph 5.4.2)
Load turned OFF The load power has been cut o
Powered from Output
Start-up error. Voltage present on the UPS output.
A skilled technician must check the UPS connections.
Turned Off with charged H.V.bus
The UPS has not shutdown properly. Make sure the DC buses are discharged
before performing any maintenance operation on the UPS.
Saving NVData error
Error saving some UPS parameters. If the problem persists, contact the
LEGRAND Technical Support Service.
Invalid CM SW Versions:
Execute update!
The command boards have been programmed with dierent software
versions. The software versions must be aligned by carrying out an update of
the command boards through a PC.