Trimod HE
User manual
47
Input electrical characteristics
3 104 22
3 104 31
3 104 42
3 104 43
3 104 44
3 104 02
3 103 96
3 103 9
10 kVA
3 104 23
3 104 33
3 104 45
3 104 46
3 104 07
3 104 08
3 104 03
15 kVA
3 104 23
3 104 32
3 104 33
3 104 47
3 104 48
3 104 13
3 104 14
3 104 09
20 kVA
3 104 25
3 104 68
30 kVA TM
3 104 24
3 104 34
3 104 69
3 104 18
3 104 17
3 104 15
30 kVA TT
3 104 26
3 104 71
3 104 19
40 kVA
3 104 27
3 104 72
3 104 20
60 kVA
3 104 73
80 kVA
Maximum three-phase/
three-phase current
19.2 A 28.8 A 38.4 A 57.6 A 57.6 A 76.8 A 115.2 A 153.6 A
Maximum three-phase/
single-phase current
19.2 A 28.8 A 38.4 A 57.6 A - - - -
Maximum single-phase/
three-phase current
57.6 A 86.4 A 115.2 A 172.8 A - - - -
Maximum single-phase/
single-phase current
57.6 A 86.4 A 115.2 A 172.8 A - - - -
Nominal input voltage
230 V + 15% - 20% (Single-phase)
400 V + 15% - 20% (Three-phase)
(neutral line indispensable)
400 V + 15% - 20% (Three-phase)
(neutral line indispensable)
Input frequency
50 / 60 Hz ± 2%
50 / 60 Hz ± 14 %
(autosensing and/or selectable by the user)
Power factor on input > 0.99
Total harmonic distortion
of the input current
THDi < 3%