Trimod HE
User manual
53
Environmental conditions
3 104 22
3 104 31
3 104 42
3 104 43
3 104 44
3 104 02
3 103 96
3 103 97
10 kVA
3 104 23
3 104 33
3 104 45
3 104 46
3 104 07
3 104 08
3 104 03
15 kVA
3 104 23
3 104 32
3 104 33
3 104 47
3 104 48
3 104 13
3 104 14
3 104 09
20 kVA
3 104 25
3 104 68
30 kVA TM
3 104 24
3 104 34
3 104 69
3 104 18
3 104 17
3 104 15
30 kVA TT
3 104 26
3 104 71
3 104 19
40 kVA
3 104 27
3 104 72
3 104 20
60 kVA
3 104 73
80 kVA
Operating temperature 0 ÷ 40 °C
Relative humidity during
operation
0% ÷ 95% non condensing
Storage temperature -20°C ÷ 50 °C (excluding batteries)
Noise level at 1 metre 58 ÷ 62 dBA
Pollution degree PD2
Environmental category
(EN 60721-3-3)
3K2
Protection index IP 20
Operating height up to 1000 metres above sea level without derating
Trimod HE 3 108 51 battery charger module (BCM) technical specications
Nominal input voltage 230 Vac + 15% - 20%
Nominal input voltage 19.3 A
Input power factor PF > 0.99
Total harmonic distortion
of the input current
THDi < 3%
Nominal output voltage 240/252 Vdc
Output voltage in
maintenance phase
13.75 Vdc per battery
Nominal input voltage 15 Adc max
AC/DC performance >93% at max rated output current
Functioning status
indications
(signalled by
multicoloured LED on
module and indications
on UPS display)
Yellow LED, fast ashing: recharge phase f1
Green LED, slow ashing: recharge phase and maintenance f2
Green LED steady: standby
Red LED: fault status
Reference directive and standards
Marchi CE, EAC, CMIM
Safety
2014/35/EU Directive
EN 62040-1
EMC
2014/30/EU Directive
EN 62040-2
Performance and test
requirements
EN 62040-3