WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer or
equivalent, service agency, or the gas supplier.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of
refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992.
Approved methods of recovery, recycling or reclaiming
must be followed. Fines and/or incarceration may be
levied for noncompliance.
IMPORTANT
This unit must be matched with an indoor coil as
specied in Lennox Product Specication bulletin. Coils
previously charged with HCFC-22 must be ushed.
CAUTION
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
WARNING
Electric Shock Hazard. Can cause injury or
death. Unit must be properly grounded in
accordance with national and local codes.
Line voltage is present at all components
when unit is not in operation on units with
single-pole contactors. Disconnect all remote
electric power supplies before opening
access panel. Unit may have multiple power
supplies.
16HPX
Table of Contents
Installation Clearances ...................................................2
Model Number Identication ...........................................2
Dimensions .....................................................................3
Specications .................................................................4
Typical Unit Parts Arrangement ...................................... 5
Operating Gauge Set and Service Valves ......................5
Unit Placement ..............................................................7
Removing and Installing Louvered Panels .....................8
New or Replacement Line Set ........................................9
Brazing Connections ................................................... 11
Flushing Line Set and Indoor Coil ................................14
Installing Indoor Metering Device .................................15
Leak Test Line Set and Indoor Coil ..............................16
Evacuating Line Set and Indoor Coil ...........................17
Electrical .......................................................................18
System Operation .......................................................20
System Conguration ...................................................20
Defrost System ...........................................................23
Maintenance ...............................................................25
Wiring and Sequence of Operation ...........................27
Servicing Units Void of Charge ...................................31
Start-Up ......................................................................31
Service Literature
UNIT INFORMATION
Corp. 1912-L8
August 9, 2019
16HPX (HFC-410A) SERIES OUTDOOR UNITS
General Information
These instructions are intended as a general guide and do
not supersede national or local codes in any way. Consult
authorities having jurisdiction before installation.
The Merit® 16HPX model is designed for use with HFC-
410A refrigerant only. This unit must be installed with
an approved indoor air handler or coil. See the Lennox
16HPX Product Specication bulletin (EHB) for approved
indoor component matchups.
This outdoor unit is designed for use in systems that use
the following refrigerant metering device:
Check thermal expansion valve (CTXV)

Other manuals for Lennox 16HPX-048

Question and Answer IconNeed help?

Do you have a question about the Lennox 16HPX-048 and is the answer not in the manual?

Lennox 16HPX-048 Specifications

General IconGeneral
TypeHeat Pump
SEER Rating16
HSPF Rating9.5
RefrigerantR-410A
Compressor TypeScroll
Sound Level74 dB
StagesSingle
Voltage208/230V
Phase1
Maximum Operating Temperature (Cooling)115°F
Cooling Capacity48000 BTU/h
Heating Capacity48000 BTU/h

Summary

Installation Clearances

Specifications

Operating Gauge Set and Service Valves

Torque Requirements

Provides recommended torque values for fasteners used during service.

Using Manifold Gauge Set

Details the type of manifold gauge set required for HFC-410A systems.

Operating Service Valves

Explains the function and operation of liquid and vapor line service valves.

Service Valves Angle and Ball

Operating Angle Type Service Valve

Describes the procedure for operating angle-type service valves.

Operating Ball Type Service Valve

Describes the procedure for operating ball-type service valves.

Unit Placement

Positioning Considerations

Discusses factors to consider when positioning the unit for optimal performance and noise.

Placing Unit on Slab

Provides guidance on how to properly place the unit on a level slab.

New or Replacement Line Set

Refrigerant Line Set

Covers information on selecting and installing refrigerant line sets.

Matching with New or Existing Indoor Coil and Line Set

Details how to match the outdoor unit with compatible indoor coils and line sets.

Line Set Isolation

Explains the importance of isolating refrigerant lines to prevent vibration.

Line Set Installation

Brazing Connections

Brazing Procedures

Brazing Procedures (continued)

Braze Line Set

Details the process of brazing the line set, emphasizing cooling and safety.

Flushing Line Set and Indoor Coil

Flushing Line Set

Details the procedure for flushing the refrigerant lines and indoor coil.

Installing Indoor Metering Device

Leak Test Line Set and Indoor Coil

Test for Leaks

Outlines the procedure for performing a leak test on the system.

Evacuating Line Set and Indoor Coil

Evacuate the System

Details the procedure for evacuating the refrigerant lines and indoor coil to remove moisture.

Size Circuit and Install Service Disconnect Switch

System Operation

System Configuration

Introduces the demand defrost control and its function.

Demand Defrost Control (A108)

Defrost System

Maintenance

Heat Pump Operation

Wiring and Sequence of Operation

16HPX Operating Sequence

Servicing Units Void of Charge

Start-Up

Start-Up and Performance Checklist