Page 9
SURELIGHT INTEGRATED CONTROL BOARD
FIGURE 6
XFMR-N
Flame
sense
4-Flame Sensor 80UHG -2 models
A flame sensor is located on the left side of the burner
support.  See  figure  8.  The  sensor  is  mounted  on  a
bracket  in the  burner  support and  the  tip protrudes
into the flame envelope of the left-most burner. The
sensor is fastened to burner supports and can be reĆ
moved for service without removing any part of the
burners. During operation, flame is sensed by current
passed through the flame and sensing electrode. The
SureLight control allows the gas valve to remain open
as long as flame signal is sensed.
NOTE  -  The  80UHG    furnace  contains  electronic
components that are polarity sensitive. Make sure that
the  furnace  is  wired  correctly  and  is  properly
grounded.
PARK
TERMINAL DESIGNATIONS
COOL-H
HEAT-H
EAC-H
HUM-H
XFMR-H
LINE-H
LINE-N
HUM-N
EAC-N
XFMR-N
CIR-N
Blower - Cooling Speed (120VAC)
Blower - Heating Speed (120VAC)
Electronic Air Cleaner (120VAC)
Humidifier (120VAC)
Transformer (120VAC)
Input (120VAC)
Input (Neutral)
Humidifier (Neutral)
Electronic Air Cleaner (Neutral)
Transformer (Neutral)
Not Used
(FLAME SENSE)
TABLE 4
SURELIGHT IGNITOR
SureLight Ignitor
FIGURE 8
NORMAL FLAME SIGNAL  u 0.2 MICROAMPS
LOW FLAME SIGNAL         v 0.2 MICROAMPS
MINIMUM  FLAME SIGNAL v 0.15 MICROAMPS
BURNER
FLAME
SENSOR
SIDE VIEW END VIEW
1/4 in. 7 mm
 1/32 in. 0.79
mm
3/16 in.
4.7 mm
11/16 in. 18 mm
 1/32 in. 0.79
mm