EasyManuals Logo

Lennox CBX27UH User Manual

Lennox CBX27UH
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
Page 11
CBX27UH SERIES
Making Electrical Connections
WARNING
Run 24V Class II wiring only through specified low volt-
age opening. Run line voltage wiring only through speci-
fied high voltage opening. Do not combine voltage in one
opening.
CAUTION
USE COPPER CONDUCTORS ONLY.
This unit is provided with knock-outs for conduit. Refer to
figure 12 on page 13 for unit wiring diagram, which includes
all field wiring. Separate openings have been provided for
24V low voltage and line voltage. Refer to the dimension
illustration on page 2 or 3 for specific location.
Wiring must conform to the current National Electric Code
ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA
Standard C22.1, and local building codes. Refer to
following wiring diagrams. See unit nameplate for
minimum circuit ampacity and maximum overcurrent
protection size.
Select the proper supply circuit conductors in
accordance with tables 310−16 and 310−17 in the
National Electric Code, ANSI/NFPA No. 70 or tables 1
through 4 in the Canadian Electric Code, Part I, CSA
Standard C22.1.
The motor speed is set by the speed tap connection to the
low voltage terminal strip in the control section. The speed
can be increased by swapping wires as shown in figure 10.
WIRING CONNECTIONS
1. Install line voltage power supply to unit from a properly
circuit breaker.
2. Ground unit at unit disconnect switch or to an earth
ground.
NOTE  Connect conduit to the unit using a proper
conduit fitting. Units are approved for use only with
copper conductors. A complete unit wiring diagram is
located on the back side of the unit’s access panel.
3. Install low voltage wiring from outdoor to indoor unit
and from thermostat to indoor unit.
NOTE  For proper voltages, select thermostat wire
gauge per the following chart:
Table 7. Run Length (Class II Rated Wiring)
Wire Run Length AWG # Insulation/Core Types
Less than 100’ (30m) 18
Color−coded, temperature
rating 95
º
F (35
º
C) minimum,
solid core.
More than 100’ (30m) 16
NOTE  Units are approved for use only with copper conductors.
Ground unit at disconnect switch or to an earth ground.
NOTE  24VAC, Class II circuit
connections are made in the con-
trol panel.
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet (1.5m)
from the floor. It should not be installed on an outside wall or where it
can be affected by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CBX27UH and is the answer not in the manual?

Lennox CBX27UH Specifications

General IconGeneral
TypeAir Handler
BrandLennox
ModelCBX27UH
EfficiencyUp to 16 SEER
RefrigerantR-410A
Heating CapacityVaries by model
Nominal Heating CapacityVaries by model
AirflowUp to 2000 CFM
Coil TypeAluminum
Voltage208/230V
Sound LevelQuiet operation
HeightVaries by model
WidthVaries by model
LengthVaries by model
WeightVaries by model
Nominal Cooling Capacity1.5 to 5 tons
Motor TypeECM
Cabinet ConstructionHeavy-gauge, painted steel
InsulationFully insulated

Related product manuals