• 20 •
1
/
2
7
/8”
1
08
5/8”
1-1
/8”
17
7
5/8”
1-
3/8”
1
82
3/
4
1-
3/8”
2
65
3/
4
1-
5/8”
27
7
/8”
1-
5/8”
3
74
020S 025S 030S 035S 040S 045D 055D 070D 080D 100D
C1
1/2” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 5/8” 3/4”
C2
n/a n/a n/a n/a n/a 5/8” 5/8” 5/8” 5/8” 5/8”
C1
7/8” 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 5/8”
C2
n/a n/a n/a n/a n/a 1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 3/8”
61281812128181212
C1
5/8” 5/8” 5/8” 3/4” 3/4” 5/8” 5/8” 3/4” 3/4” 7/8”
C2
n/a n/a n/a n/a n/a 5/8” 5/8” 3/4” 3/4” 3/4”
C1
1 1/8” 1 1/8” 1 3/8” 1 3/8” 1 5/8” 1 1/8” 1 3/8” 1 3/8” 1 5/8” 1 5/8”
C2
n/a n/a n/a n/a n/a 1 1/8” 1 3/8” 1 3/8” 1 5/8” 1 5/8”
12 18 18 18 18 18 18 18 18 12
Installation, Operation and Maintenance manual • CSC/CSH-MIL153E-1217-05/2018
TABLE 1: REFRIGERANT LINES SELECTION
From 40 m to 65 meters , the long distance kit is required.
n/a: not available
- IN MODEL 100D THE REFRIGERANT PIPES ARE FROM DIFFERENT SIZE . THE BIGEST SIZE CORRES-
PONDS TO CIRCUIT C1 AND THE SMALLEST ONE TO THE C2 CIRCUIT
The unit is supplied with brazing connections. As an option , the unit can be supplied with gas precharge from the fac-
tory ; in that case only the TABLE 2 has to be taken into account. ( this option includes the service valves).
TABLE 2 : EXTRA REFRIGERANT CHARGE R410A BY METER OF COPPER PIPE
L
i
q
uid
G
as
g
r
/m
The unit is precharged from factory with nytrogene . The installer should remove this gas and charge the units
with the charge of refrigerant R410A , shown in the following tables plus the charge by additional meter shown in
the TABLE 2
In the double circuit units , check before connecting C1 and C2 circuits , that they are the same circuit for the indoor
and the outdoor section
REFRIGERANT LINES
UNIT - MODEL
Total line length
(refrigerant line
length between
indoor and
ourtoor units)
0 to 30 m.
(Standard
conection
unit)
Ø Lquid
Ø Gas
Max. n
er
of bends
30 to 65 m.
Ø Liquid
Ø Gas
Max. n
er
of bends
2.7- REFRIGERANT CONNECTIONS
2.- INSTALLATION
Legislation does not allow refrigerant gas emissions to the atmosphere, so the refrigerants have to be recy-
cled to avoid being released to the atmosphere. Those recycled refrigerants shall be processed afterwards
by an authorized waste manager.
Those components derived from the recycling of the unit have to be managed by authorized waste manager
or be left in local waste facilities according the local normative in each country.