• 5 •
055D
14000 16000 18000 20000 21400
741 299 264 225 160 96
709 271 235 195 137 83
677 242 206 165 113 70
645 213 178 135 73 57
613 184 149 105 32 44
070D
14700 16800 18900 21000 22400
741 272 230 182 122 66
709 243 201 153 98 50
677 213 172 124 74 33
645 184 142 95 44 16
613 154 113 66 13 -0.4
085D
15400 17600 19800 22000 23500
751 277 235 187 126 69
719 247 199 159 101 51
686 208 162 120 71 36
654 181 139 89 24 15
621 154 112 65 12 n/a
020S
5300 6100 6850 7600 8100
751 178 156 134 104 77
719 162 140 118 89 64
686 141 118 96 67 38
654 124 101 78 47 6
621 108 86 64 35
(rpm)
(m3/h)
025S
5950 6800 8500 9100
841 223 195 126 91
805 202 174 107 74
769 177 148 88 44
732 154 125 63 7
696 135 107 40 4
(rpm)
(m3/h)
030S
7000 8000 9000 10000
934 272 234 194 142
894 246 208 168 117
854 213 175 134 84
814 186 146 106 55
773 161 123 82 36
(rpm)
(m3/h)
035S
8400 9600 10800 12000 12850
741 209 191 171 146 125
709 189 171 152 126 105
677 168 151 132 107 87
645 148 131 112 88 68
613 128 111 92 69 50
(rpm)
(m3/h)
040S
8200 9350 10525 11700 12500
741 205 188 170 148
709 185 168 150 128 110
677 163 146 128 106 89
645 143 127 109 87 68
613 126110916951
(rpm)
(m3/h)
045D
9800 11200 12600 14000
829 237 213 183 136
794 235 187 156 111
758 233 161 130 86
722 231 135 104 72
686 229 109 77 57
(rpm)
(m3/h)
100D (C1)
10850 12400 13950 15500 16600
846 239 210 171 125
801 207 180 138 92 58
756 175 150 105 58 26
711 143 121 72 26 n/a
666 111 91 39 n/a n/a
(rpm)
(m3/h)
100D (C2)
8200 9350 10525 11700 12500
743 201 187 157 141 119
711 199 167 136 161 101
679 197 148 116 102 83
647 195 128 95 84 64
615 193 108 75 65 46
(rpm)
(m3/h)
(rpm)
(m3/h)
(rpm)
(m3/h)
(rpm)
(m3/h)
•
•
•
Installation, Operation and Maintenance manual • CSC/CSH-MIL153E-1217-05/2018
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Pulley closed
1 turn
2 turns
3 turns
4 turns
Illegal position because of the limit of engine power Note: The unit leaves factory with the pulley fi t to 2 open turns
1.4.- FAN PERFORMANCES (Available static pressure Pa.)
STANDARD UNITS WITHOUT OPTIONALS
1.- GENERAL CHARACTERISTICS