Page 27
TABLE 11 
Unit
High Altitude Pressure Switch 
4501 - 7500 ft
Natuarl LP/Propane
-040 20K91 N/A
-060 No Change No Change
-080 No Change N/A
-100 20K91 N/A
Other Unit Adjustments
Primary Limit
The primary limit is located on the heating compartment 
vestibule panel. The secondary limits (if equipped) are lo-
cated in the blower compartment, attached to the back 
side of the blower. These auto reset limits are factory-set 
and require no adjustment.
Thermal Switch
These manually reset switches are located on the front of 
the box.
Pressure Switch
The pressure switch is located in the heating compartment 
adjacent to the combustion air inducer. The switch checks 
for proper combustion air inducer operation before allow-
ing ignition trial. The switch is factory-set and requires no 
adjustment.
Temperature Rise
After the furnace has been started, and supply and return 
air temperatures have been allowed to stabilize, check the 
temperature rise. If necessary, adjust the blower speed to 
maintain the temperature rise within the range shown on 
the unit nameplate. See TABLE 11 for allowable heating 
speeds.Increase the blower speed to decrease the tem-
perature. Decrease the blower speed to increase the tem-
perature rise. Failure to adjust the temperature rise may 
cause erratic limit operation.
Fan Control
The heat fan-on time of 30 seconds is not adjustable. The
heat fan-o delay  (amount  of time  that  the blower  oper-
ates  after  the  heat  demand  has  been  satised)  may  be 
adjusted by changing the jumper position across the ve 
pins on the integrated control. The unit is shipped with a 
factory fan-o delay setting of 90 seconds. The fan-o de-
lay aects  comfort and  is adjustable to satisfy individual 
applications. Adjust the fan-o delay to achieve a supply 
air temperature between 90° and 110°F at the moment 
that the blower is de-energized. Longer o delay settings 
provide lower return air temperatures; shorter settings 
provide higher return air temperatures. See FIGURE 26.
Constant Torque Motor
EL180UHNE units are equipped with a constant torque 
ECM motor. It has a DC motor coupled to an electronic 
control module both contained in the same motor hous-
ing. The motor is programmed to provide constant torque 
at each of the ve selectable speeds. The motor has ve 
speed taps. Each tap requires 24 volts to energize.
HEAT FAN‐OFF TIME IN SECONDS
To adjust fan-off timing, reposition jumper across pins to
achieve desired setting.
NO JUMPER
60
90
120
180
60
90
120
180
60
90
120
180
60
90
120
180
60 Second 
off Time
90 Second 
off Time
120 Second 
off Time
180 Second 
off Time
FIGURE 26 
Input Voltage Requirements
The circuit is designed to be operated with AC voltage. A 
voltage of 12 to 33VAC is required to energize the motor. 
Expected current draw will be less than 20mA.
Blower Speeds
Follow the steps below to change the blower speeds.
1 -  1 - Turn o electrical power to furnace.
2 -  Remove blower access panel.
3 -  Disconnect existing speed tap at integrated control 
speed terminal.
NOTE - Termination of any unused motor leads must be 
insulated.
4 -  Place unused blower speed tap on integrated control 
“PARK” terminal or insulate.
5 -  Refer to blower speed selection chart on unit wiring 
diagram for desired heating or cooling speed. 
See  Product  Specications  manual  for  blower 
performance data. See TABLE 11 for allowable 
heating speeds.
6 -  Connect selected speed tap at integrated control 
speed terminal.
7 - Resecure blower access panel.
8 - Turn on electrical power to furnace.
9 - Recheck temperature rise.
Electronic Ignition
The integrated control has an added feature of an internal 
Watchguard control. The feature serves as an automat-
ic reset device for integrated control lockout caused by 
ignition failure. This type of lockout is usually due to low 
gas line pressure. After one hour of continuous thermostat 
demand for heat, the Watchguard will re-set and remake 
thermostat demand to the furnace and automatically reset 
the integrated control to begin the ignition sequence.