Page 12
7KH(/8+(IXUQDFHFDQEHLQVWDOOHGLQKRUL]RQWDODS-
plications with either right- or left-hand air discharge.
5HIHU WR )LJXUH IRU FOHDUDQFHV LQ KRUL]RQWDO DSSOLFD-
tions.
Horizontal Application
Installation Clearances
dnE thgiRdnE tfeL
Right-Hand Discharge
Left-Hand Discharge
Top
Bottom (Floor)**
Bottom (Floor)**
dnE thgiRdnE tfeL
Air
Flow
Air
Flow
AIR FLOW
AIR FLOW
Top 0
Front* 0
Back 0
Ends 0
Vent 0
Floor 0‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
**An 8” service clearance must be maintained below the unit to
provide for servicing of the condensate trap.
‡For installations on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
Figure 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawl-
space. Either suspend the furnace from roof rafters or
ÀRRUMRLVWV DVVKRZQLQ)LJXUH RULQVWDOOWKHIXUQDFH
RQ D SODWIRUP DV VKRZQ LQ )LJXUH $ KRUL]RQWDO VXV-
pension kit (51W10) may be ordered from Lennox or use
equivalent.
NOTE - +HDY\JDXJHVKHHWPHWDOVWUDSVPD\EHXVHGWR
VXVSHQGWKHXQLWIURPURRIUDIWHUVRUFHLOLQJMRLVWV:KHQ
VWUDSVDUH XVHG WRVXVSHQGWKHXQLWLQ WKLV ZD\VXSSRUW
PXVWEHSURYLGHGIRUERWKWKHHQGV7KHVWUDSVPXVWQRW
LQWHUIHUH ZLWK WKH SOHQXP RU H[KDXVW SLSLQJ LQVWDOODWLRQ
Cooling coils and supply and return air plenums must
be supported separately.
HORIZONTAL SUSPENSION KIT
Bracket
(typical)
Metal Strap
(typical)
Air
Flow
Internal Brace
(provided with kit)
Figure 18
NOTE - :KHQWKHIXUQDFHLVLQVWDOOHGRQDSODWIRUPRUZLWK
WKHKRUL]RQWDOVXVSHQVLRQNLWLQDFUDZOVSDFHLWPXVWEH
HOHYDWHG HQRXJK WR DYRLG ZDWHU GDPDJH DFFRPPRGDWH
GUDLQWUDSDQGWRDOORZWKHHYDSRUDWRUFRLOWRGUDLQ
Platform Installation of Horizontal Unit
1 - Select location for unit keeping in mind service and
other necessary clearances. See Figure 17.
2 - Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above
¿QLVKHGVSDFHIDEULFDWHDQDX[LOLDU\GUDLQSDQWREH
installed under unit. Set unit in drain pan as shown
in Figure 19. Leave 8 inches for service clearance
below unit for condensate trap.
3 - Provide a service platform in front of unit. When
installing the unit in a crawl space, a proper support
platform may be created using cement blocks.
4 - Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.