IOM / ROOF-TOP FLEXY™ Series - Page 81
This option is used for making a connection to the BMS only,
by a set of hard contacts.
It requires the addition of a KP05 card, if this is not already in
place, and a KP12 card.
Input connection must be by screened cable only.
Limits of relays :
• 10A – 250V with resistive load
• 4A – 250V with inductive load.
BMS VOLT FREE CONTACTS KIT
DRY CONTACT KIT FOR BMS / REMOTE SET POINT
STOP CONTROL
NIGHT CONTROL
DAY CONTROL
50% LOAD SHEDDING
HEAT LOAD SHEDDING
COLD LOAD SHEDDING
FAULT RESETTING
FILTER FAULT
TREATMENT FAN FAULT
COMPRESSOR FAULT
GAS BURNER FAULT
ELECTRICAL RESISTANCE FAULT
TOP LIMIT TEMPERATURE FAULT
BOTTOM LIMIT TEMPERATURE FAULT
HUMIDIFIER FAULT