BLOWER DATA
AIR RESISTANCE
HORIZONTAL AIRFLOW APPLICATIONS
Air Volume
Standard Static
Power Exhaust fans
or
No Power Exhaust Fans
50% High Static
Power Exhaust Fans
100% High Static
Power Exhaust Fans
cfm in. w.g. in. w.g. in. w.g.
10,000 .20 .23 .25
10,500 .20 .25 .30
11,000 .20 .25 .30
11,500 .20 .30 .40
12,000 .20 .33 .45
12,500 .20 .35 .50
13,000 .20 .38 .55
13,500 .25 .43 .60
14,000 .25 .45 .65
14,500 .25 .48 .70
15,000 .30 .55 .80
15,500 .30 .58 .85
16,000 .30 .63 .95
16,500 .30 .63 .95
17,000 .30 .68 1.05
17,500 .30 .70 1.10
18,000 .30 .75 1.20
18,500 .30 .78 1.25
19,000 .30 .83 1.35
19,500 .30 .83 1.40
20,000 .30 .90 1.50
20,500 .35 .94 1.60
21,000 .35 .98 1.70
21,500 .35 1.02 1.80
22,000 .35 1.04 1.90
22,500 .35 1.10 2.00