EasyManuals Logo

Lennox LGH480 User Manual

Lennox LGH480
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
Page 45
507232-04 7/2017
Step 5. ALL TEMPERATURE MODES OF OPERATION
In the Economizer – Temperature mode, the damper opens
for free cooling when the outdoor air temperature is:
Less than return air temperature by at least a difference
of (Parameter 161 - ECON FRCL TMP OFFST) if
Temperature Offset mode is selected
Less than (Parameter 160 - ECON FREECL TEMP SP)
In all modes, dampers will try to modulate discharge air
temperature (RT6) to (Parameter 159 - FREE COOL
SUPPLY SP) which has a default setting of 55.0°F (13°C).
Refer to the “Displaying Sensor Inputs" section to read
return air (RT16) and outdoor air (RT17) temperatures. If
outdoor air is not cooler than return air, simulate a colder
outdoor air temperature with a resistor. Select a resistor
value that corresponds to a temperature (see table 21):
A Locate RT17 sensor in unit. Disconnect 1/4" quick
connect terminals on wires leading from sensor.
B Jumper RT17 wires leading back to control with the
appropriate resistor.
C Check all connections and wiring between RT17 and
the M3 Unit Controller, and between RT16 and the M3
Unit Controller.
TABLE 21
TMP MODE RESISTOR VALUES
Temp.
°F
(°C)
Size
Resist
or
Temp
. °F
(°C)
Size
Resist
or
Temp
. °F
(°C)
Size
Resist
or
Temp
. °F
(°C)
Size
Resist
or
30
(-1)
34,56
6
50
(10)
19,90
4
70
(21)
11,88
4
90
(32)
7,332
40 (
4)
26,10
6
60
(16)
15,31
3
80
(27)
9,298 100
(38)
5,826
Step 6. GLOBAL MODULATING (GLO) MODE OF
OPERATION
In the GLO (modulating) mode, dampers modulate open for
free cooling when the global input is energized; dampers
will try to modulate discharge air temperature (RT6) to
(Parameter 159 - FREE COOL SUPPLY SP) which has a
default setting of 55.0°F (13°C).
NOTE - The global input turns on the blower.
A Set global mode using the Configuration ID 1,
position 2, and set to character G.
B Connect a jumper between A55_P297-1 (24VAC) and
A55_P297-9 (global). The blower will be energized and
the damper will slowly open if discharge air temperature
(RT6) is greater than (Parameter 159 - FREE COOL
SUPPLY SP) which has a default setting of 55.0°F
(13°C).
C Disconnect 24VAC to A55_P297-9. The blower will turn
off and the damper will close.
D If the damper does not actuate check all connections
and wiring between P262A and B.
Step 7. ENTHALPY SENSOR OPERATION (A7 and
A62)
A Connect a direct current ammeter as shown in figure 39
to measure current output of A7 or A62.
NOTE - If Enthalpy Sensors are configured, current sensor
reading by M3 controller can be verified on User interface:
B The reading will be between 4 and 20 ma. depending on
outdoor temperature and humidity. Refer to figure 37 to
approximate reading.
Go to DATA > IN/OUTPUTS > SENSORS > LOCAL
(scroll down to IE: x.x mA and OE: x.x mA)
C If the meter reads zero, check sensor wiring harness for
continuity and/or check polarity of sensor wiring.
DISCONNECT J/P104
PLACE JUMPER WIRE HERE
READ
CURRENT
HERE
DC AMMETER
-
+
Damper Travel: % of Maximum Open
DISCONNECT J/P105
PLACE JUMPER WIRE HERE
READ
CURRENT
HERE
DC AMMETER
-
+
Measure A62 Current in SeriesMeasure A7 Current in Series
MEASURE A7 AND A62 CURRENT IN SERIES
FIGURE 39

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox LGH480 and is the answer not in the manual?

Lennox LGH480 Specifications

General IconGeneral
BrandLennox
ModelLGH480
CategoryAir Conditioner
LanguageEnglish

Related product manuals