Page 33
Turning O Gas to Unit
1 -   If using an electromechanical thermostat, set to the 
lowest setting.
2 -  
power to the appliance.
3 -   Open or remove the control access panel.
4 -   Move gas valve switch(es) to OFF.
  Close or replace the control access panel.
WHITE RODGERS 36J54 GAS VALVE
Two-Stage
Gas valve switch is shown in OFF position.
LOW FIRE
ADJUSTMENT
HIGH FIRE
ADJUSTMENT
INLET
PRESSURE
TAP
MANIFOLD
PRESSURE TAP
FIGURE 23 
C-Cooling Start up
A-Operation
1 -   Initiate full load cooling operation using the following 
mobile service app menu path:
(COOL 4 on 074U units)
2 -   Units contain one refrigerant circuit or stage.
3 -   Unit is charged with R-410A refrigerant. See unit 
rating plate for correct amount of charge.
4 -   Refer to charging section method to check 
refrigerant charge.
D-Safety or Emergency Shutdown
IV-CHARGING
A-Refrigerant Charge and Check - Fin/Tube Coil
WARNING-Do not exceed nameplate charge under 
any condition.
This unit is factory charged and should require no further 
adjustment. If the system requires additional refrigerant, 
reclaim the charge, evacuate the system, and add re-
quired nameplate charge.
NOTE - System charging is not recommended below 60°F 
(15°C). In temperatures  below 60°F  (15°C) , the  charge 
must be weighed into the system.
If weighing facilities are not available, or to check the 
charge, use the following procedure:
1 -   Attach gauge manifolds and operate unit in cooling 
mode on HIGH SPEED with economizer disabled 
Make sure outdoor air dampers are closed.
Note - Use mobile service app menu path SERVICE 
> TEST > COOL > COOL 3 for 036, 048 and 060U 
units. Use COOL 4 for 074U units.
2 -   Use a thermometer to accurately measure the 
outdoor ambient temperature.
3 -   Apply the outdoor temperature to tables 6 through 9 
to determine normal operating pressures. Pressures 
4 -   Compare the normal operating pressures to 
the pressures obtained from the gauges. Minor 
variations in these pressures may be expected due 
could mean that the system is not properly charged 
or that a problem exists with some component in 
the system. Correct any system problems before 
proceeding.
  If discharge pressure is high, remove refrigerant 
from the system. If discharge pressure is low, add 
refrigerant to the system.
•  Add or remove charge in increments.
•   Allow the system to stabilize each time refrigerant is 
added or removed.
6 -        
methods along with the normal operating pressures 
B-Subcooling Method - Ultra High Eciency Units
1 -   Attach gauge manifold to the liquid line. With the 
economizer disabled, operate the unit in cooling 
mode at high speed using the following mobile 
service app menu path:
(COOL 4 on 074U units)
2 -   Use the liquid line pressure and a PT chart to 
determin  the saturated liquid temperature.
3 -   Measure the liquid line temperature at the condenser 
outlet. 
Subcooling Temperature = Liquid Saturated Tempera-
ture Minus Liquid Temperature.
4 -   The subcooling temperature should be as shown 
this value indicates an overcharge. A subcooling 
temperature less than this value indicates an 
undercharge.