When checking piping connection for gas leaks, use the 
preferred means. Common kitchen detergents can cause 
harmful corrosion on various metals used in gas piping. 
The use of specialty Gas Leak Detector is strongly rec-
ommended.
Do  not  use  matches,  candles,  ame  or  any  other 
source of ignition to check for gas leaks.
GAS VALVE
CAP
MANUAL MAIN
SHUT-OFF VALVE
PRESSURE TEST GAS LINE
FIGURE 25 
3-Testing Gas Supply Pressure
When testing gas supply pressure, connect test gauge to 
the inlet pressure tap located on unit gas valve GV1. Test 
stages energized). Make sure the reading falls within the 
range of the following values. Low pressure may result in 
natural gas units, operating pressure at the unit gas con-
gas units, operating pressure at the unit gas connection 
On multiple unit installations, each unit should be checked 
separately while operating at maximum rate, beginning 
with the one closest to the supply gas main and progress-
ing to the one furthest from the main. Multiple units should 
also be tested with and without the other units operating. 
Supply pressure must fall within the range listed in the 
previous paragraph.
4-Check and Adjust Manifold Pressure
After line pressure has been checked and adjusted, check 
manifold pressure. Move test gauge to the outlet pressure 
-
tion of pressure tap on the gas valve.
The manifold pressure is factory set and should not re-
quire adjustment. See table 4. If manifold pressure is in-
correct and no other source of improper manifold pressure 
for location of gas valve (manifold pressure) adjustment 
screw.
All gas valves are factory regulated. The gas valve should 
 CAUTION
For  safety,  connect  a  shut-o  valve  between  the 
manometer and the gas tap to permit shut o of gas 
pressure to the manometer.
Manifold Adjustment Procedure
1 -   Connect test gauge to the outlet pressure tap on the 
gas valve. Start the unit (call for second stage heat) 
state.
2 -   While waiting for the unit to stabilize, notice the 
and should not lift from the burner heads. Natural 
gas should burn basically blue with some clear 
streaks. L.P. gas should burn mostly blue with some 
clear yellow streaks.
3 -  
record the manifold pressure and compare to the 
values given in table 4. On two-stage units, check 
       
before recording values.
Combustion gases
Flue products must be analyzed and compared to the unit 
     
may make it necessary to temporarily shut down the fur-
nace until the items can be repaired or replaced.
5-Proper Gas Flow 
-
         -
tions of gas through the meter. (Two revolutions assures 
a more accurate time.) Divide by two and compare to time 
in table 11. Seconds in table 11 are based on a 1 ft.3. dial 
    
ft3’ for LP. Adjust manifold pressure on gas valve to match 
time needed.
NOTE - To obtain accurate reading, shut o all other gas 
appliances connected to meter.