EasyManua.ls Logo

Lennox LGM Series - Electrical Data - 25 Ton; Voltage & Compressor Data (25 Ton); Fan & Blower Data (25 Ton); Overcurrent Protection & Ampacity (25 Ton)

Lennox LGM Series
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 15
ELECTRICAL DATA 25 TON
Model No. LGM300U4
1
Voltage - 60Hz 208/230V-3ph 460V-3ph 575V-3ph
Compressor 1 Rated Load Amps   7.1
Locked Rotor Amps 21 11 12
Compressor 2 Rated Load Amps  8.2 
Locked Rotor Amps   55.3
Compressor 3 Rated Load Amps 22.4  7.7
Locked Rotor Amps  75 54
Compressor 4 Rated Load Amps 22.4  7.7
Locked Rotor Amps  75 54
Outdoor Fan

Full Load Amps
(total)
2.8

1.4
(8.4)
1.1

Power Exhaust
(2) 0.33 HP
Full Load Amps
(total)
2.4
(4.8)
1.3

1
(2)
Service Outlet 115V GFI (amps) 15 15 20
Indoor Blower
Motor
Horsepower 5 7.5 10 5 7.5 10 5 7.5 10
Full Load Amps  24.2 30.8  11 14  11
2
Maximum
Overcurrent
Protection (MOCP)
Unit Only 125 150 150  70 70 50 50 
With (2) 0.33 HP
Power Exhaust
150 150 150 70 70 80 50 50 
3
Minimum
Circuit
Ampacity (MCA)
Unit Only 121  137 57   44 47 50
With (2) 0.33 HP
Power Exhaust
 134 142      52
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.