Page 37
V- SYSTEMS SERVICE CHECKS
A-Heating System Service Checks
Before checking piping, check with gas company or au-
thorities having jurisdiction for local code requirements. 
Refer to the LGM Installation, Operation and Maintenance 
instruction for more information.
1-Gas Piping
Gas supply piping must not allow more than 0.5”W.C. 
(124.3 Pa) drop in pressure between the gas meter and 
the unit. Supply gas pipe must not be smaller than the 
unit gas connection. Refer to installation instructions for 
details.
2-Testing Gas Piping
power to the unit. These controls should be properly la-
beled by the installer.
When pressure testing gas lines, the gas valve must be 
disconnected and isolated. Gas valves can be damaged 
.
When checking piping connection for gas leaks, use the 
preferred means. Common kitchen detergents can cause 
harmful corrosion on various metals used in gas piping. 
The use of specialty Gas Leak Detector is strongly rec-
ommended. It is available through under part number 
31B2001. See CORP 8411-L10, for further details.
ignition to check for gas leaks.
UNIT
GROUND
JOINT UNION
MANUAL MAIN
SHUT-OFF VALVE
(REFER TO LOCAL CODES)
GAS PIPING
SUPPORT
DRIP LEG
ROOF
MOUNTING
FRAME
GAS PIPING COMPONENTS
REFER TO INSTALLATION INSTRUCTIONS
VALVE
CAP HERE
TO ISOLATE
VALVE WHEN
PRESSURE
TESTING
LINE
FIGURE 26 
3-Testing Gas Supply Pressure
When testing gas supply pressure, connect test gauge to 
the inlet pressure tap located on unit gas valve GV1 and 
-
mum rate (both stages energized).
Make sure the reading falls within the range of the follow-
ing values. Low pressure may result in erratic operation or 
  -
pressures.
On multiple unit installations, each unit should be checked 
separately while operating at maximum rate, beginning 
with the one closest to the supply gas main and progress-
ing to the one furthest from the main. Multiple units should 
also be tested with and without the other units operating. 
Supply pressure must fall within the range listed in the 
previous paragraph.
4-Check and Adjust Manifold Pressure
After line pressure has been checked and adjusted, check 
manifold pressure. Move test gauge to the outlet pressure 
25 for location of pressure tap on the gas valve.
The manifold pressure is factory set and should not re-
quire adjustment. If manifold pressure is incorrect and no 
other source of improper manifold pressure can be found, 
gas valve (manifold pressure) adjustment screw.
All gas valves are factory regulated. The gas valve should 
 CAUTION
       
pressure to the manometer.
Manifold Adjustment Procedure
1 -   Connect test gauge to the outlet pressure tap on the 
gas valve. Start the unit (call for second stage heat) 
state.
2 -   While waiting for the unit to stabilize, notice the 
and should not lift from the burner heads. Natural 
gas should burn basically blue with some clear 
streaks. L.P. gas should burn mostly blue with some 
clear yellow streaks.
3 -  
record the manifold pressure and compare to the 
values given in table 20.
 CAUTION
Disconnect heating demand as soon as an accurate 
reading has been obtained.