Page 48
IX--Multi-Staged Blower
       -
tached to the unit (table 18 in the installation instructions) 
-
ed, set the medium cooling CFM at the high or low cooling 
design spec or any CFM between.
B-Set Maximum CFM
Use attached table to determine highest blower CFM for 
appropriate unit. Adjust the blower pulley to deliver that 
amount of CFM with only the blower operating. See D ter-
mining Unit CFM in the Blower Operation and Adjustment 
section.
C-Set Blower Speeds
1 -  1. Use the following mobile service app menu to 
        
Controller. Make sure blower CFM is within limitations 
shown in table 24 or 25 . Refer to the Unit Controller 
manual provided with unit.
RTU MENU > RTU OPTIONS > BLOWER > SPEED
2 -  
in the attached table (table18 in the installation 
instructions).
Blower / Heat CFM
Cooling High CFM
Cooling Low CFM
Vent CFM
3 -   Adjust the blower RPM to deliver the target CFM 
based on the measured static pressure using the 
blower table.
4 -   Measure the static pressure again and apply the 
static pressure and RPM to the blower tables to 
determine adjusted CFM.
5 -   Repeat adjustments until design CFM is reached.
D-Set Damper Minimum Position
To maintain required minimum ventilation air volumes 
when the unit is in the occupied mode, two minimum 
damper positions must be set.
The Unit Controller will open the damper to “Min OCP Blwr 
High” when blower CFM is at or ABOVE the “midpoint”
CFM.
The  Unit  Controller  will  open  the  dampers  to  “Min  OCP 
Blwr Low” when blower CFM is BELOW a “midpoint” CFM.
The Unit Controller will calculate the “midpoint” CFM.
*Available blower speeds vary by unit and thermostat 
stages.
Set Minimum Position 1
Use the following mobile service app menu to set “Min 
OCP Blwr High” for the blower CFM above the “midpoint” 
CFM. When navigating into this menu, the Unit Controller 
will run damper calibration and allow damper position ad-
justment.
RTU MENU > SETTINGS > RTU OPTIONS > DAMPER
Tap “Next” to skip tabs and complete damper position cal-
ibration until “Damper Calibration Blower Speed High” tab
appears.
Measure the intake air CFM. If the CFM is lower than the 
-
troller to increase the damper percent open. If the CFM is 
NOTE - Intake air CFM can also be determined using the 
outdoor air temperature, return air temperature and mixed 
air  temperature.  Refer  to  the  economizer  or  outdoor  air 
damper installation instructions.
Set Minimum Position 2
Use the following mobile service app menu in the Unit 
Controller to set “Min OCP Blwr Low” for the blower CFM 
below the “midpoint” CFM. When navigating into this 
menu, the Unit Controller will run damper calibration and 
allow damper position adjustment.
RTU MENU > SETTINGS > RTU OPTIONS > DAMPER
Tap “Next” to skip tabs and complete damper position cal-
ibration until “Damper Calibration Blower Speed High” tab 
appears.Measure the intake air CFM. If the CFM is lower 
Unit Controller to increase the damper percent open. If 
        
percent open.
Note - Intake air CFM can also be determined using the 
outdoor air temperature, return air temperature and mixed 
air  temperature.  Refer  to  the  economizer  or  outdoor  air 
damper installation instructions.
E-Inverter Bypass Option
The supply air inverter is factory-set to by-pass the invert-
er manually. To by-pass the inverter and operate the blow-
er in the constant air volume mode, use the following Unit 
Controller menu and set to “engaged”:
SETTINGS > RTU OPTIONS > BLOWER > VFD BYPASS
use the following Unit Controller menu.
SETUP > INSTALL
Press SAVE until the menu reads:
CONFIGURATION ID 1
-
pass option.
Press SAVE
Caution - Units not equipped with an inverter will have the
6th  character  set  to  N,  indicating  the  inverter  is  not  by-
passed. The blower motor could be damaged and/or result
in product or property damage if the setting is changed to
automatic or manual.