EasyManuals Logo

Lennox LGM Series User Manual

Lennox LGM Series
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
Page 50
X-VAV System
Units contain a supply air blower equipped with a variable

     

A-Start-Up
1 - A pressure transducer (A30) is shipped in a box
in the blower compartment. Install the transducer
according to manufacturer’s instructions.
Note - Make sure the transducer is installed in the
main duct at least 2/3 of the distance away from the
unit.
2 - Two twisted pairs of shielded cable must be used to

P378 connector is hanging in the control box.
3 - Open all zone dampers and/or boxes.
4 - 
5 - Use the mobile service app to calibrate the blower
CFM. Select this menu to start the blower:
SETUP > TEST & BALANCE > BLOWER
The mobile app will display the percent of blower speed.
       

 Press NEXT and follow the instructions to calibrate
static pressure. If the static pressure meets the
      
setpoint. If the static pressure does not meet the

NEXT to set the setpoint.
7 - 
8 - If the desired CFM cannot be met with current
pulley setup, refer to the Blower Operation and
Adjustments section to adjust CFM.
TABLE 26
RECORD ADJUSTED SETPOINTS
Parameter
Setpoint
Description
Setpoint
“w.c.
Display
Setting
 Smoke
387 Ventilation
388 Heating
 Cooling
PRESSURE TRANSDUCER WIRING
TWISTED
PAIR
UNUSED WIRE
DRAIN
NOT
CONNECTED
NOT
CONNECTED
TWISTED
PAIR
A30
+S
_
+
P378
1
2
3
FIGURE 36
Note - The Unit Controller will lock-out the unit for 5 min-
utes if static pressure exceeds 2.0”w.c. for 20 seconds.
The Unit Controller will permanently shut down the unit af-
ter three occurrences. See mobile service app parameters
110, 42, and 43 to adjust default values.
CONTROL AREA
A96
SUPPLY AIR VFD
Figure 37

Other manuals for Lennox LGM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox LGM Series and is the answer not in the manual?

Lennox LGM Series Specifications

General IconGeneral
BrandLennox
ModelLGM Series
CategoryFurnace
LanguageEnglish

Related product manuals