SPECIFICATIONS - GAS HEAT
Usage Data Model Number LGM156
LGM180
LGM210
LGM156
LGM180
LGM210
LGM240
LGM300
LGM180
LGM210
LGM240
LGM300
Heat Input Type    
Number of Gas Heat Stages 1 2 2 2
Gas Heating
Performance

Input - Btuh First Stage   234,000 312,000
Second Stage N/A   480,000
Output - Btuh First Stage 135,000 - - - - - - - - -
Second Stage N/A 208,000 288,000 384,000
1
Gas Heating
Performance

Input - Btuh First Stage N/A 84,500 117,000 
Second Stage N/A  234,000 312,000
Third Stage N/A 214,000  
Fourth Stage N/A   480,000
Output - Btuh First Stage 135,000 - - - - - - - - -
Second Stage N/A - - - - - - - - -
Third Stage N/A - - - - - - - - -
Fourth Stage N/A 208,000 288,000 384,000
 15 - 45 15 - 45  40 - 70
󰀩 80.0% 80.0% 80.0% 80.0%
Gas Supply Connections 1 in. npt 1 in. npt 1 in. npt 1 in. npt
Recommended Gas Supply
Pressure - in. w.g.
Natural 7 7 7 7
LPG/Propane 11 11 11 11
1
Four-stage gas heating is enabled when room sensor, Discharge Air Control, or fresh air tempering mode is selected. (Available when using the CS8500 thermostat or
when connected to Building Automation Systems using BACnet, LonTalk, or S-Bus protocols)
HIGH ALTITUDE DERATE

At altitudes above 2000 feet, units must be derated to match gas manifold pressures shown in table below.
At altitudes above 4500 feet unit must be derated 2% for each 1000 feet above sea level.

TWO-STAGE
Gas Heat
Type

Altitude - ft. Gas Manifold Pressure - in. w.g. Input Rate
Natural Gas or LPG/Propane - Btuh
Natural Gas LPG/Propane Gas First
Stage
Second
Stage
Low (L) No adjustment required
Standard (S) 2001 - 4500 3.4   
Medium (M) 2001 - 4500 3.4  234,000 345,000
High (H) 2001 - 4500 3.4  312,000 
FOUR-STAGE
1
Gas Heat
Type

Altitude - ft. Gas Manifold Pressure - in. w.g. Input Rate
Natural Gas or LPG/Propane - Btuh
Natural Gas LPG/Propane Gas First
Stage
Second
Stage
Third
Stage
Fourth
Stage
Low (L) No adjustment required
Standard (S) 2001 - 4500 3.4  84,000   
Medium (M) 2001 - 4500 3.4  117,000 234,000  345,000
High (H) 2001 - 4500 3.4   312,000  
1


Other manuals for Lennox LGM Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox LGM Series and is the answer not in the manual?

Lennox LGM Series Specifications

General IconGeneral
BrandLennox
ModelLGM Series
CategoryFurnace
LanguageEnglish

Related product manuals