Page 31
sensing electrode, gas valve and combustion air blower. 
       
valve are directly controlled by ignition control. Ignition 
control and combustion air blower is controlled by Unit 
Controller A55.
Burners
         
Burners are factory set and do not require adjustment. 
A peep hole with cover is furnished in the heating ac-
with the access panel in place.
Burners can be removed individually for service. Burn-
er maintenance and service is detailed in the SERVICE 
CHECKS section of this manual.
TYPICAL GAS BURNER ASSEMBLY
BURNERS
ORIFICE
SENSOR
BURNER
SUPPORT
BURNER
SUPPORT CAP
FIGURE 19 
ORIFICE WITH
PIPE THREADS
Tighten to 6.25 + .5 ft.lbs.
Do not over-tighten.
Tighten to 14 + .5 ft/lbs
 Do not over-tighten.
ORIFICE WITH
STRAIGHT THREADS
FIGURE 20 
Orice
is precisely matched to the burner input. Install only the 
into the burner manifold. The burner is supported by 
NOTE-Do not use thread sealing compound on the or-
ices.  Using  thread  sealing  compound  may  plug  the 
orices.
        
unit. Refer to Repair Parts Listing for correct sizing in-
formation. 
NOTE- In primary and secondary high temperature limits 
S10 and S99 the ignition circuits in both gas heat sections 
one  and  two  are  immediately  de-energized  when  termi-
nals 1-3 open and the indoor blower motor is immediately 
energized  when  terminals  1-2  close.  This  is  the  primary 
and secondary safety shut-down function of the unit.
4-Primary High Temperature Limits S10 & S99
S10 is the primary high temperature limit for gas heat sec-
gas heat section two.
shield behind the blower housing. In this location S10 and 
Primary limit S10 is wired to the Unit Controller A55 which 
wired to the A55 Unit Controller which energizes burner 2 
control (A12). Its N.C. contacts open to de-energize the 
ignition control when excessive temperature is reached in 
the blower compartment. At the same time, the N.O. con-
K3 through control A55. If either limit trips the blower will 
be energized. Limits settings are factory set and cannot 
be adjusted. If limit must be replaced same type and set 
point must be used. See Repair Parts Handbook.
S10 and S99 Location
CONDENSER
DIVIDER
PANEL
S10 AND S99 ON
HIND BLOWER
HOUSING
GAS HEAT
SECTION 1
GAS HEAT
SECTION 2
FIGURE 21