MERIT
®
CBX25UHV SERIES
Table 5. Merit
®
CBX25UHV‐030 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed First-Stage “COOL” Speed Second-Stage “COOL” Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 650 900 1100 1320 430 600 740 920 650 875 1100 1330
NORM 590 795 1000 1200 390 550 680 830 580 800 1000 1200
520 730 895 1075 340 475 620 750 500 700 900 1090
NOTES 
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications  minimum blower speed is 250 cfm.
Table 6. Merit
®
CBX25UHV‐036 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed First-Stage “COOL” Speed Second-Stage “COOL” Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 880 1115 1345 1435 615 770 930 1090 880 1110 1340 1435
NORM 800 1010 1215 1425 555 695 845 990 795 1005 1215 1420
715 905 1095 1275 505 625 755 885 715 905 1090 1280
NOTES 
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications  minimum blower speed is 250 cfm.
Table 7. Merit
®
CBX25UHV‐042 Air Handler Performance (0 through 0.80 in. w.g. [0 — 200 Pa] External Static Pressure Range)
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed First-Stage “COOL” Speed Second-Stage “COOL” Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 1115 1345 1560 1800 800 960 1120 1265 1130 1360 1580 1800
NORM 1025 1215 1415 1630 730 870 1020 1150 1040 1240 1450 1640
925 1110 1280 1460 650 790 915 1050 950 1120 1290 1470
NOTES 
The effect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First-stage cooling air volume is 70% of COOL (second-stage) speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications  minimum blower speed is 450 cfm.