13
not operate in this mode. The Follow Me mode is
only available when a return air sensor is utilized.
Typically in most cases the Follow Me mode will
not be sufcient to remove excessive humidity.
NOTE: In addition, the outdoor units do not have a
humidistat installed therefore they are unable to
determine humidity levels. This product is not
recommend as a main source for dehumidication.
Note, this well over shoot the temperature by 6-8
degrees below what was set for dry mode.
NOTE: Using this mode will over shoot the temp by 6-8
degrees below what was set for dry mode.
6.3.2. Dry Mode Operation Sequence
Whenindry modeoperationthe unit isactuallyin cooling
modewithalowspeed bloweroperation.Thecompressor
willstopwhentheroomtemperatureistwodegreesCelsius
lowerthanthetemperaturesetting.
However there is a temperature compensation for cooling
modethatistwodegreesCelsius.Sotheunitwillstopwhen
thetemperatureisfourdegreesCelsiuslowerthantheroom
temperaturesettings.
NOTE: Four degrees Celsius is equivalent to 8°F
difference.
6.4. Test Run - Indoor Units
Onlyperformtestrunafteryouhavecompletedthefollowing
steps:
• ElectricalSafetyChecks–Conrmthattheunit’s
electricalsystemissafeandoperatingproperly
• GasLeakChecks–Checkallarenutconnectionsand
conrmthatthesystemisnotleaking
• Conrmthatgasandliquid(highandlowpressure)
valvesarefullyopen.
6.4.1. Test Run Instructions
YoushouldperformtheTestRunforatleast30minutes.
1. Connectpowertotheunit.
2. PresstheON/OFFbuttonontheremotecontrollertoturn
it on.
3. Press the mode button to scroll through the functions,
oneatatime:
4. Leteach function run forveminutes, and perform the
followingchecks:
6.4.2. Before Test Run
Table 3. Test Run Checklist
Checks Pass Fail
Noelectricalleakage
Unitisproperlygrounded
Allelectricalterminals
properlycovered
Indoorandoutdoorunits
aresolidlyinstalled
Allpipeconnectionpoints
donotleak
Waterdrainsproperlyfrom
drainhose
Allpipingisproperly
insulated
UnitperformsCOOL
functionproperly
Indoorunitlouversrotate
properly
Indoorunitrespondsto
remotecontroller
6.5. Double-Check Pipe Connections
Duringoperation,thepressureoftherefrigerantcircuitwill
increase.Thismayrevealleaksthatwerenotpresentduring
your initial leak check. Take time during the Test Run to
double-checkthatall refrigerantpipeconnection points do
nothaveleaks.
• Usingremotecontrol,returnunittothenormal
operatingtemperature.
• Usinginsulationtape,wraptheindoorrefrigerantpipe
connectionsthatyouleftuncoveredduringtheindoor
unitinstallationprocess.
6.6. Ambient Temperature is Below 63°F
(17°C)
You can’t use the remote controller to turn on the COOL
function when the ambient temperature is below 17°C. In
thisinstance,youcanusetheMANUALCONTROLbutton
totesttheCOOLfunction.
• Liftthefrontpaneloftheindoorunit,andraiseituntilit
clicksinplace.
• TheMANUALCONTROLbuttonislocatedontheright-
handsideoftheunit.Pressitonetimetoselectthe
COOLfunction.FirstpushisFCforcecooling,which
willdisplayonthewallunitasFCwhichisusedforhigh
speedcharging30minutetime.
• PerformTestRunasnormal.
• PushthebuttononetimeisforFCforcecooling,which
willdisplayedonwallunitasFC.Thisisusedforhigh
speedcharging30minutetime.
• Pushthebuttontwotimesforcoolingset75ºFandunit
isinautomode.Temperatureissetat75°Fwithno
changingofsettemperature..