EasyManua.ls Logo

Lennox MWHA018S4-1P - Gas Leak Check With Soap Water; Air And Moisture; Air Purging Using A Vacuum Pump; Adding Refrigerant if Pipe Length Exceeds Charge Less Pipe Length

Lennox MWHA018S4-1P
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
12.1. Gas Leak Check with Soap Water:
Apply soap water or a liquid neutral detergent on the
connectionswithasoftbrushtocheckforleakageinthepipe
connectingpoints.Ifbubblesemerge,thepipesareleaking.
12.2. Air and Moisture
Airandmoistureintherefrigerantsystemcausethefollowing
problems:
Increasesinsystempressure
Increasesinoperatingcurrent
Decreasesincoolingandheatingefciency
Blocksincapillarytubingcausedbymoistureinthe
refrigerantcircuitfreezing
Corrosionofpartsintherefrigerantsystemcausedby
water
Theindoorunitsandthepipesbetweenindoorandoutdoor
unitsmustbetestedforleakagesandevacuatedtoremove
gasandmoisturefromthesystem.
12.3. Air Purging using a Vacuum Pump
Completelytightenthearenutsontheindoorand
outdoorunits.Conrmthatboththetwo-wayandthree-
wayvalvesaresettotheclosedposition.
Connectthechargehosewiththepushpinofthe
HandleLotothethree-wayvalvegasserviceport.
ConnectthechargehoseoftheHandleHitothe
vacuumpump.
FullyopentheHandleLoofthemanifoldvalve.
Turnonthevacuumpumptobeginevacuation.
Conducta30-minuteevacuation.Checkwhether
thecompoundmeterindicates-0.1Mpa(14.5Psi).If
themeterdoesnotindicate-0.1Mpa(14.5Psi)after
30minuteshaselapsed,continueevacuationfor20
moreminutes.Ifthepressuredoesnotreach-0.1Mpa
(14.5Psi)after50minuteshaselapsed,checkifthere
areanyleaks.
FullyclosetheHandleLovalveofthemanifoldvalve
andturnoffthevacuumpump.Afterveminutes,
conrmthatthegaugeneedleisnotmoving.
Turnthearenutonthethree-wayvalve45°counter-
clockwisefor6-7seconds.Oncegasbeginstocome
out,tightenthearenut.Makesurethepressure
displayonthepressureindicatorishigherthan
atmosphericpressure.Thenremovethechargehose
fromthethree-wayvalve.
Fullyopenthetwo-wayandthree-wayvalvesand
securelytightenthecaponthethree-wayvalve.
12.4. Adding Refrigerant if Pipe Length Exceeds
Charge Less Pipe Length
Connectthechargehosetothechargingcylinderandopen
the two-way and three-way valves. With the charge hose
youdisconnectedfromthevacuumpump,connectittothe
valveatthebottomofthecylinder.
IftherefrigerantisR-410A,placethecylinderbottom-upto
ensureliquidchargingispossible.
Purgetheairfromthechargehose.
Openthevalveatthebottomofthecylinderandpress
thecheckvalveonthechargeset(becarefulofthe
liquidrefrigerant).
Placethechargingcylinderontotheelectronicscale
andrecordtheweight.
Turnontheairconditionerincoolingmode.
Openthevalves(Lowside)onthechargeset.Charge
thesystemwithliquidrefrigerant.
Whentheelectronicscaledisplaystheproperweight
(refertothetable),disconnectthechargehosefrom
thethree-wayvalve’sserviceportimmediatelyandturn
offtheairconditionerbeforedisconnectingthehose.
MountthevalvestemcapsandtheserviceportUse
atorquewrenchtotightentheserviceportcaptoa
torqueof18N.m(13.27ft·lbs).
Besuretocheckforgasleaks.
12.5. Add Refrigerant after Long-Term System
Operation
Connectthechargehosetothethree-wayserviceport
andopenthetwo-wayandthree-wayvalve.
Connectthechargehosetothevalveatthebottom
ofthecylinder.IftherefrigerantisR-410A,placethe
cylinderbottom-uptoensureliquidcharge.
Purgetheairfromthechargehose.
Openthevalveatthebottomofthecylinderandpress
thecheckvalveonthechargesettopurgetheair(be
carefuloftheliquidrefrigerant).
Placethechargingcylinderontotheelectronicscale
andrecordtheweight.
Turnontheairconditionerincoolingmode.
Openthevalves(Lowside)onthechargesetand
chargethesystemwithliquidrefrigerant.
Whentheelectronicscaledisplaystheproperweight
(refertothegaugeandthepressureofthelowside),
disconnectthechargehosefromthethree-wayvalve’s
serviceportimmediatelyandturnofftheairconditioner
beforedisconnectingthehose.
Mountthevalvestemcapsandtheserviceport.Use
torquewrenchtotightentheserviceportcaptoa
torqueof18N.m(13.27ft·lbs).

Table of Contents

Other manuals for Lennox MWHA018S4-1P

Related product manuals