Page 30
Troubleshooting: Burner runs continuously (too little heat).
Source Procedure Causes Correction
Combustion
Check burner
combustion for
CO2, stack tem
perature, and
smoke
Low CO
2
less
than 10%.
Too much combustion air Reduce combustion air.
Air leaks into heat exchanger
around inspection door, etc.
Correct cause of air leak.
Excessive overfire draft
Adjust barometric draft con
trol for correct draft.
Incorrect nozzle assembly
depth
Set to 1.13.
High smoke
reading more
than a trace.
Dirty or plugged heat exchanger
Clean heat exchanger.
Readjust burner.
Insufficient overfire draft Increase draft.
Incorrect nozzle assembly
depth
Set to 1.13.
Too little combustion air Increase combustion air.
High stack tem
perature is
more than
550
_F Net.
Low volume indoor blower air
Check pump coupling for
wear / slippage.
Dirty heat exchanger Clean heat exchanger.
Dirty burner blower wheel Clean burner blower wheel.
Dirty furnace air filters Clean or replace filter.
Restricted or closed registers or
dampers
Readjust registers or damp
ers.
Oil Pressure
Inspect fire and check
oil pressure.
Partially plugged or bad nozzle Replace nozzle.
Oil pressure is too low
(less than 140 psi.)
Increase oil pressure to 140
psi.