EasyManuals Logo

Lennox SL280DF110V60C Unit Information

Lennox SL280DF110V60C
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
Page 25
DIP Switch Settings
NOTE - All communicating settings are set at the commu-
nicating thermostat. See thermostat installation instruc-
tion. In a communication system all DIP switch and clippa-
ble link settings are ignored. For conventional thermostats
proceed with DIP switch and clippable link settings as out-
lined in the following.
Heating Operation DIP Switch Settings
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch
which must be properly positioned for the particular appli-
cation. The DIP switch is factory-positioned for use with a
twostage thermostat. If a single-stage thermostat is to be
used, the DIP switch must be repositioned.
a. Select “OFF” for two-stage heating operation controlled by a
two-stage heating thermostat (factory setting);
b. Select “ON” for two-stage heating operation controlled by
a single-stage heating thermostat. This setting provides a
timed delay before second-stage heat is initiated.
Switch 2 -- Second Stage Delay (Used with Single-
Stage Thermostat Only) -- This switch is used to de-
termine the second stage on delay when a single-stage
thermostat is being used. The switch is factory-set in the
OFF position, which provides a 7-minute delay before
secondstage heat is initiated. If the switch is toggled to
the ON position, it will provide a 12-minute delay before
secondstage heat is initiated. This switch is only activated
when the thermostat selector jumper is positioned for SIN-
GLEstage thermostat use.
Switches 3 and 4 -- Blower-O󰀨 Delay -- The blower-on
delay of 30 seconds is not adjustable. The blower-o󰀨 de-
lay (time that the blower operates after the heating de-
mand has been satised) can be adjusted by moving
switches 3 and 4 on the integrated control. The unit is
shipped from the factory with a blower-o󰀨 delay of 90 sec-
onds. The blower o󰀨 delay a󰀨ects comfort and is adjust-
able to satisfy individual applications. Adjust the blower
o󰀨 delay to achieve a supply air temperature between 90°
and 110°F at the exact moment that the blower is de-en-
ergized. Longer o󰀨 delay settings provide lower supply
air temperatures; shorter settings provide higher supply
air temperatures.TABLE 6 provides the blower o󰀨 timings
that will result from di󰀨erent switch settings.
TABLE 6
Blower O󰀨 Delay Switch Settings
Blower O󰀨 Delay
(Seconds)
Switch 3 Switch 4
60 On O󰀨
90 (factory) O󰀨 O󰀨
120 O󰀨 O󰀨
180 On O󰀨
Indoor Blower Operation DIP Switch Settings
Switches 5 and 6 -- Cooling Mode Blower Speed --
The unit is shipped from the factory with the dip switch-
es positioned for high speed (4) indoor blower motor op-
eration during the cooling mode. TABLE 7 provides the
cooling mode blower speeds that will result from di󰀨erent
switch settings. Switches 5 and 6 set the blower cfm for
secondstage cool. The integrated control automatically
ramps down to 70% of the second-stage cfm for rst-stage
cfm. Refer to blower tables for corresponding cfm values.
TABLE 7
Cooling Mode Blower Speeds
Speed Switch 5 Switch 6
Low On On
Medium Low O󰀨 On
Medium High On O󰀨
High (Factory) O󰀨 O󰀨
Switches 7 and 8 -- Cooling Blower Speed Adjustment
-- The unit is shipped from the factory with the dip switches
positioned for NORMAL (no) adjustment. The dip switches
may be positioned to adjust the blower speed by +10% or
-10% to better suit the application. TABLE 8 below pro-
vides blower speed adjustments that will result from di󰀨er-
ent switch settings. Refer to blower tables for correspond-
ing cfm values.
TABLE 8
Cooling Blower Speed Adjustment
Adjustment Switch 7 Switch 8
+10% (approx.) On O󰀨
Factory Default O󰀨 O󰀨
-10% (approx.) O󰀨 On
Switches 9 and 10 -- Cooling Mode Blower Speed
Ramping -- Blower speed ramping may be used to en-
hance dehumidication performance. The switches are
factory set at option A which has the greatest e󰀨ect on de-
humidication performance. TABLE 9 provides the cooling
mode blower speed ramping options that will result from
di󰀨erent switch settings. The cooling mode blower speed
ramping options are detailed below.
NOTE - The o portion of the selected ramp prole also
applies during heat pump operation in dual fuel applica-
tions.
TABLE 9
Cooling Mode Speed Ramping
Ramping Option Switch 9 Switch 10
A (factory) O󰀨 O󰀨
B O󰀨 On
C On O󰀨
D On On

Other manuals for Lennox SL280DF110V60C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox SL280DF110V60C and is the answer not in the manual?

Lennox SL280DF110V60C Specifications

General IconGeneral
BrandLennox
ModelSL280DF110V60C
CategoryFurnace
LanguageEnglish

Related product manuals