Note!
Parameter set transfer between devices with different firmware versions
ƒ For devices with firmware versions 2.0 ... 6.3, the motor magnetising current is
calculated internally within the controller. You cannot adapt it to your application.
ƒ For devices with firmware versions 7.0 ... 7.2, you can adapt the motor magnetising
current to your application using the new code C0095.
Therefore the motor magnetising current in C0095 is not updated if a parameter set
transfer of devices with firmware versions 2.0 ... 6.3 to devices with firmware versions
7.0 ... 7.2 is carried out.
How to update the motor magnetising current after you have transferred the parameter sets
Transferring parameter sets Updating the motor magnetising current
Controller
with firmware version
Controller
with firmware version
What do you have to do?
2.0 ... 6.3 2.0 ... 6.3 Nothing
2.0 ... 6.3 7.0 ... 7.2 Confirm the operating mode after a parameter set transfer in C0006
has been effected. Thus, the correct motor magnetising current is
calculated and entered in C0095.
7.0 ... 7.2 7.0 ... 7.2 Nothing
7.0 ... 7.2 2.0 ... 6.3 Nothing
Confirming mode of operation
Via keypad Via Global Drive Control (GDC)
1. Change to the code level and select C0002 in the ”Code list”
menu.
Open the ”Code list” menu in the parameter menu.
2. Change to the parameter level of C0002. Click on C 0002 and select ”Load PS1” from the dialog box.
3. SelectC0002=1(LoadPS1)andconfirmtheselectionby
+ .
Confirm by ”Ok”.
4. Change to the parameter level of C0006. The active
operating mode is displayed.
Click on C0006. In the dialog box the active operating mode
is highlighted.
5. Confirm the setting by + .
The correct motor magnetising current is calculated
automatically and is entered in C0095.
Confirm the setting by ”Ok”. The correct motor
magnetising current is calculated automatically and is
entered i n C0095.
If you press F7, the current value in C0095 is displayed.
6. Change to the parameter level of C0003. Click on C 0003 and select ”Save PS1” from the dialog box.
7. SelectC0003=1(SavePS1)andconfirmtheselectionby
+ .
Confirm by ”Ok”.
8. Repeat the steps 2. to 7. for each parameter set that you
have transferred.
Repeat the steps 2. to 7. for each parameter set that you
have transferred.