Wiring the installation backplane
Important notes
5
46
EDK94ZPP0364 ZH/EN 2.0
5 Wiring the installation backplane
5.1 Important notes
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Switch off the power supply and wait for at least three minutes
before working on t he power terminals.
ƒ Make sure that all power terminals are deenergised.
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when the device is touched in the event
of a fault.
Protective measures:
ƒ Implement the actions required in the EN 61800-5-1. Especially:
Fixed installation
PE connection must conform to standards (PE conductor
diameter 10 mm
2
or PE conductor must be connected twice)