EasyManua.ls Logo

Lenze 9400 Series - Design of the Cables; How to Connect the Shield

Lenze 9400 Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring the installation backplane
Wiring
Design of the cables
5
53
EDK94ZPP0364 ZH/EN 2.0
5.3.3 Design of the cables
ƒ The cables used m ust comply with the approvals required for the location
(e.g. UL).
ƒ It is imperative to comply with the regulations concerning minimum
cross-sections of PE conductors. The cross-section of the PE conductor
must be at least as large as the cross-section of the power connections.
ƒ The effectiveness of a shielded cable is reached by:
Providing a good shield connection through large-surface shield
contact.
Using only braided shields with low shield resistance made of tin-plated
or nickel-plated copper braid.
Using braided shields with an overlap rate > 70 % and an overlap angle
of 90 °.
Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
ƒ External brake resistor ( Mounting Instructions of the brake resistor)
The following connections need not be shielded:
ƒ Mains
ƒ DC bus
5.3.4 How to connect the shield
E94AZPS004
Fig. 5-5 Connect the shield to the shield sheet (graphics on the right: motor cable for device sizes
II and III)