EasyManuals Logo

Lenze ECSxK001 series User Manual

Lenze ECSxK001 series
483 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
Commissioning
Optimising the drive behaviour after start
Adjustment of field controller and field weakening controller
6
145
EDBCSXA064 EN 3.2
6.13.2.1 Adjusting the field controller
The field controller settings depend on the motor data.
Setting sequence
1. Stop the PLC program: C2108 = 2
As of operating system version 7.0 (see nameplate), this is no longer necessary,
because C0006 (see 2.) can also be written when the PLC program is running!
2. Set motor control for asynchronous motors: C0006 = 2
The motor nameplate data must be entered correctly!
3. Read rotor time constant T
r
(C0083).
4. Read magnetising current I
d
(C0092).
5. Calculate field controller gain V
pF
and enter in C0077.
V
pF
+
T
r
(C0083) @ I
d
(C0092)
875ms @ I
max
I
max
Maximum current of axis module
6. Enter rotor time constant T
r
as field controller integral−action time T
nF
in C0078.

Table of Contents

Other manuals for Lenze ECSxK001 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze ECSxK001 series and is the answer not in the manual?

Lenze ECSxK001 series Specifications

General IconGeneral
BrandLenze
ModelECSxK001 series
CategoryControl Unit
LanguageEnglish

Related product manuals