5 Commissioning
Addressing
EDKMF2133 DE/EN/FR 4.0
62
H2 Adressierung-SetSlaveAdress
Address settings through the front DIP switch
The address (decimal number) is calculated by inserting the different switch states S1 ... S7
(’0’ = OFF and ’1’ = ON) into t he equation:
Address
dec
= S
1
⋅ 2
0
+ S
2
⋅ 2
1
+ S
3
⋅ 2
2
+ S
4
⋅ 2
3
+ S
5
⋅ 2
4
+ S
6
⋅ 2
5
+ S
7
⋅ 2
6
The equation also allows to find out about the valency of a switch (see front label). The sum
of valencies results in the station address to be set:
Switch S1 S2 S3 S4 S5 S6 S7
Valency 1 2 4 8 16 32 64
Example 1:
Switch S1 S2 S3 S4 S5 S6 S7
Switch position 1 1 1 0 0 0 0
Address (= 7) 1 2 4 0 0 0 0
Example 2:
Switch S1 S2 S3 S4 S5 S6 S7
Switch position 1 0 0 1 1 0 0
Address (= 25) 1 0 0 8 16 0 0