Commissioning
Addressing
5
EDKMF2133 DE/EN/FR 4.0
63
H2 Adressierung-SetSlaveAdress
Address settings through keypad or PC
Addresses are set using code C0009 (see controller code table)
DIP switches S1 - S7 must be in OFF position (= delivery state).
Address settings through the master class 2
With this method only one device must be connected to the bus. This can be achieved by a
special switch-on sequence.
Settings made through the master (master class 2) have an effect on the setting in code
C0009.
PROFIBUS station address Mapping to code C0009 (LECOM node address)
1-2 No (master addresses)
3-99 Yes (3-99)
100-125 Yes (C0009=2)
126 (LENZE setting) Yes (C0009=1)
Tab. 2 Assignment of station addresses to controllers
Note!
In the ”Power On” status, the class 2 master can set a device address via the
”Set_Slave_Address” telegram.