EasyManuals Logo

Lenze EMF2191IB User Manual

Lenze EMF2191IB
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
Technical data
Protective insulation
4
18
EDSMF2191IB EN 2.0
4.2 Protective insulation
Danger!
Dangerous electrical voltage
If Lenze controllers are used on a phase earthed mains with a rated mains
voltage 400 V, protection against accidental contact is not ensured without
implementing external measures.
Possible consequences:
ƒ Death or serious injury
Protective measures:
ƒ If protection against accidental contact is required for the control terminals
of the controller and the connections of the plugged device modules, ...
a double isolating distance must exist.
the components to be connected must be provided with the second
isolating distance.
Insulation between bus and ... Type of insulation
(in accordance with EN 61800−5−1)
l Earth reference / PE Functional insulation
l With external supply Functional insulation
l Power stage
8200 vector Reinforced insulation
9300 servo inverter Reinforced insulation
93xx servo position controller Reinforced insulation
93xx servo register control Reinforced insulation
93xx servo cam profiler Reinforced insulation
9300 vector / Servo PLC Reinforced insulation
ECS devices Reinforced insulation
l Control terminals
8200 vector Functional insulation
9300 servo inverter Basic insulation
93xx servo position controller Basic insulation
93xx servo register control Basic insulation
93xx servo cam profiler Basic insulation
9300 vector / Servo PLC Basic insulation
ECS devices Basic insulation

Other manuals for Lenze EMF2191IB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze EMF2191IB and is the answer not in the manual?

Lenze EMF2191IB Specifications

General IconGeneral
BrandLenze
ModelEMF2191IB
CategoryControl Unit
LanguageEnglish

Related product manuals