Technical data
PLC functionality
4
50
EDK10200EV3 DE/EN/FR 7.1
PLC functionality
Field Numbe
r
Description Data
Inputs
digital
8 Free inputs +24 VDC / 8 mA
per input
Reading and writing of the
inputs:
Shortest reading cycle:
1 ms (depending on the
site where the process
map is generated)
analog 3 Free inputs
(10 bits + sign)
±10 V
Outputs
digital 4 Free outputs +24 VDC / max. 1
A per output
Updating the outputs:
shortest update cycle is
1 ms (depending on the
site where the process
map is generated)
analog
1 Voltage output (10
bits + sign)
±10 V / max. 2 mA,
±0.5 %
1 Current output
(10 bits + sign)
±20 mA,
±0.5 %