Electrical installation
Terminal strips on the top of the device
6
60
EDK10200EV3 DE/EN/FR 7.1
Terminal Use Level Data
Voltage
supply
X1/^24
0 V of supply voltage,
ground for digital inputs
and outputs
− −
X1/+24 Supply voltage +18 VDC ... 30 VDC −
X1/+O24 Supply voltage for digital
outputs
+18 VDC ... 30 VDC −
Digital
inputs
X3/I1 Freely assignable input 1
HIGH active
LOW: 0 V ...+4 V
HIGH: +13 V ...+30 V
Input current: 8 mA at 24 V
Reading and processing the
inputs: shortest reading cycle:
1 ms (depending on the site
where the process map is
generated)
X3/I8 Freely assignable input 8
Digital
outputs
X2/O1 Freely assignable output
1
HIGH active
LOW: 0 V ...+4 V
HIGH: +13 V ...+30 V
Load capacity: max. 1 A per
output
Updating the outputs:
shortest update cycle is 1 ms
(depending on the site where
the process map is generated)
X2/O4 Freely assignable output
4