Instructions de mise en service
FR
SMD
Frequency Inverter
0.37 kW... 22 kW
Betriebsanleitun
DE
Instrucciones de funcionamiento
IT
Istruzioni di funzionamento
ES
Operating Instructions
EN
(13466184)

Questions and Answers

  • L
    Lisa OwensAug 23, 2025
    What to do if Lenze DC Drives show a short-circuit or overload?
    • S
      Samantha WhiteAug 25, 2025
      If the Lenze DC Drives indicate a short-circuit or overload, the cause may be a short-circuit. You should find the reason for the short-circuit and check the motor cable. It can also be caused by excessive capacitive charging current of the motor cable, in this case use shorter motor cables with lower charging current. If the acceleration time is too short, increase the acceleration time and check the controller selection. Also, check wiring if the motor cable is defective and check the motor for internal faults. If there is frequent and long overload, check the controller selection.
  • S
    Sheila CruzSep 1, 2025
    How to fix communication error on Lenze ESMD153L4TXA Inverter?
    • T
      Troy MooreSep 1, 2025
      If the Lenze Inverter reports a communication error, it could be due to the serial timer timing out. In this case, check the serial link connections.
  • G
    gthomasSep 1, 2025
    What causes undervoltage on DC bus in Lenze ESMD153L4TXA?
    • J
      Jennifer ParkerSep 2, 2025
      If the Lenze Inverter shows 'Undervoltage on DC bus', the mains voltage might be too low. Check the mains voltage to ensure it is within the required range.
  • D
    Dr. Joseph RussellSep 2, 2025
    How to resolve Lenze ESMD153L4TXA stop with inhibited outputs?
    • I
      ibarrettSep 2, 2025
      If the Lenze Inverter stops and the outputs U, V, W are inhibited, it is because there is a LOW signal at terminal 28. To solve this, set terminal 28 to HIGH.
  • P
    Paul MartinSep 3, 2025
    How to troubleshoot Dynamic braking fault on Lenze ESMD153L4TXA Inverter?
    • M
      Michael LongSep 3, 2025
      If the Lenze Inverter is showing a Dynamic braking fault, it indicates that the dynamic braking resistors are overheating. To resolve this, increase the deceleration time.
  • M
    Michael MartinezSep 4, 2025
    Why is Lenze ESMD153L4TXA Inverter output frequency 0 Hz?
    • T
      Tammy AndersonSep 4, 2025
      If the Lenze Inverter's output frequency is 0 Hz and the outputs U, V, W are inhibited, it could be due to: * Setpoint = 0 Hz (C31 = 0): In this case, you need to perform a setpoint selection. * Quick stop activated through digital input or serial link: Deactivate the Quick stop.
  • D
    David HannaSep 4, 2025
    Why are Lenze ESMD153L4TXA buttons not working?
    • A
      Anthony Marquez IVSep 4, 2025
      If the Lenze Inverter indicates that the remote keypad is active, the buttons on the front of the controller are disabled. This is normal operation when the remote keypad is in use.
  • T
    thomascaitlinSep 5, 2025
    What to do for Controller overtemperature on Lenze Inverter?
    • A
      Andrew DaughertySep 5, 2025
      If the Lenze Inverter displays 'Controller overtemperature', it means the controller is too hot inside. To resolve this, reduce the controller load and improve cooling.
  • S
    Stephanie DiazSep 6, 2025
    What does current limit reached mean on Lenze ESMD153L4TXA?
    • G
      gcookSep 6, 2025
      If the Lenze Inverter shows 'Current limit reached', it indicates a controllable overload. This is managed automatically, as described in C22.
  • C
    Cassie PopeSep 6, 2025
    How to fix No access to code on Lenze ESMD153L4TXA?
    • M
      Michele WangSep 7, 2025
      If the Lenze Inverter displays 'No access to code', it means that changes can only be made when the controller is in OFF or 1nh. To proceed, set terminal 28 to LOW or inhibit by serial link.

Summary

About These Instructions

Safety Information

General Safety

General safety precautions for Lenze controllers, covering risks from live parts and hot surfaces.

Application as Directed

Guidelines for using drive controllers in machines and compliance with EC directives like Machinery Directive.

Installation Safety

Proper handling, avoiding mechanical stress, and preventing damage to electronic components during installation.

Electrical Connection Safety

Observing national regulations and appropriate procedures for electrical installation, including cable and PE connection.

Operation Safety

Ensuring systems have monitoring/protection devices and following operational safety rules like closing covers.

Explosion Proof Applications

Policy on using inverter products with explosion proof motors, including liability and risk assumption.

Pictographs Used in Instructions

Explanation of pictographs (Danger, Warning, Stop, Note) and their consequences if ignored.

Technical Data

Standards and Application Conditions

Conformity, approvals, environmental conditions, and operating parameters for the inverter.

Ratings

Electrical ratings including input voltage, current, and output current for various inverter models.

Installation

Mechanical Installation

Guidelines for physical mounting, dimensions, and environmental considerations for the inverter.

Electrical Installation

Procedures for wiring, EMC requirements, fuses, cable cross-sections, and connection diagrams.

Commissioning

Parameter Setting

How to navigate the controller interface to set and change parameters.

Electronic Programming Module (EPM)

Information about the EPM for storing, transferring, and managing parameter settings.

Parameter Menu

Detailed description of parameter codes, possible settings, and important notes for configuration.

Troubleshooting and Fault Elimination