How to fix communication error on Lenze Inverter?
- CcookevanSep 1, 2025
If the Lenze Inverter reports a communication error, it could be due to the serial timer timing out. In this case, check the serial link connections.

How to fix communication error on Lenze Inverter?
If the Lenze Inverter reports a communication error, it could be due to the serial timer timing out. In this case, check the serial link connections.
How to troubleshoot Remote keypad fault on Lenze ESMD222L4TXA Inverter?
If the Lenze Inverter shows 'Remote keypad fault', it means the remote keypad is disconnected. To resolve this, check the remote keypad connections.
What causes motor overload on Lenze Inverter?
If the Lenze Inverter displays a motor overload (I2t overload), it means the motor is thermally overloaded. This can be due to: * Impermissible continuous current. * Frequent or excessively long acceleration processes. To resolve this: * Check the controller selection. * Check the setting of c20.
What does it mean when Lenze DC Drives reach the current limit?
Reaching the current limit in Lenze DC Drives indicates a controllable overload, which is managed automatically.
What causes overvoltage on DC bus in Lenze DC Drives and how to fix it?
Overvoltage on the DC bus in Lenze DC Drives can be caused by several factors. It may be due to mains voltage being too high, so you should check the mains voltage. Another cause can be an excessively short deceleration time or the motor operating in generator mode; in this case, increase the deceleration time or use a dynamic braking option. Finally, earth leakage on the motor side can also cause this issue, so check the motor and motor cable, separating the motor from the controller.
What to do if Lenze DC Drives show data on EPM not valid?
If Lenze DC Drives indicate that the data on the EPM is not valid, it means the data is not valid for the controller. Use an EPM providing valid data or load the Lenze setting.
What causes automatic start to be inhibited in Lenze DC Drives?
If automatic start is inhibited in Lenze DC Drives, it is because c42 = 0. You should apply a LOW-HIGH signal change at terminal 28.
How to resolve dynamic braking fault in Lenze DC Drives?
A dynamic braking fault in Lenze DC Drives typically means that the dynamic braking resistors are overheating. To resolve this, increase the deceleration time.
What to do if Lenze DC Drives show undervoltage on DC bus?
If Lenze DC Drives show undervoltage on the DC bus, it could be because the mains voltage is too low. Check the mains voltage.
What to do if Lenze DC Drives have controller overtemperature?
If the controller has an overtemperature, it means the controller is too hot inside. To resolve this, reduce the controller load and improve cooling.
| Power Rating | 2.2 kW |
|---|---|
| Input Voltage | 380-480 V AC |
| Output Voltage | 0-480 V AC |
| Protection Class | IP20 |
| Output Power | 2.2 kW |
| Type | Inverter |
| Frequency | 50/60 Hz |
| Control Method | Vector Control |
| Cooling Method | Air Cooled |
Warning about charged capacitors after power removal.
Warning about opening protective devices indicating a fault.
Provides detailed power, voltage, current, and frequency ratings for different models.
Provides dimensional drawings and mounting specs for various models.
UL requirement for fuse usage for specific voltage drives.
Details the function and configuration of various control terminal connections.
Specific guidance on meeting EMC standards, including shielding and filters.
Advises on using DC injection braking for stopping a spinning motor.
Recommendations for fuses, circuit breakers, and input power wiring.
Illustrates the electrical connections for the drive.
Warning against connecting mains power to output terminals.
Explains how to adjust operational parameters via the keypad.
Provides a detailed list and explanation of configurable parameters.
Details configuration options for digital input E1.
Warning about overwriting settings with parameter C02.
Lists error codes, their causes, and recommended remedies.
Addresses short-circuit, earth fault, and motor overload (I2t) faults.