Questions and Answers

  • R
    Robert GonzalezAug 31, 2025
    What does earth fault mean on Lenze ESMD223L4TXA?
    • A
      armstrongshellyAug 31, 2025
      If the Lenze Inverter indicates an earth fault, it could be due to: * A grounded motor phase: Inspect the motor and motor cable. * Excessive capacitive charging current of the motor cable: Use shorter motor cables with a lower charging current.
  • M
    Ms. Erika LawrenceAug 25, 2025
    Why Lenze DC Drives show earth fault?
    • A
      allenstevenAug 25, 2025
      An earth fault in Lenze DC Drives can occur if a motor phase is grounded, so you should check the motor and motor cable. It can also be due to excessive capacitive charging current of the motor cable, in this case use shorter motor cables with lower charging current.
  • B
    Bradley AndersenAug 25, 2025
    What to do if Lenze DC Drives have controller overtemperature?
    • J
      juliewilliamsAug 26, 2025
      If the controller has an overtemperature, it means the controller is too hot inside. To resolve this, reduce the controller load and improve cooling.
  • A
    Angel HillAug 26, 2025
    What to do if Lenze DC Drives show undervoltage on DC bus?
    • T
      tyler42Aug 26, 2025
      If Lenze DC Drives show undervoltage on the DC bus, it could be because the mains voltage is too low. Check the mains voltage.
  • J
    Joshua GibsonAug 27, 2025
    How to resolve dynamic braking fault in Lenze DC Drives?
    • F
      frank29Aug 27, 2025
      A dynamic braking fault in Lenze DC Drives typically means that the dynamic braking resistors are overheating. To resolve this, increase the deceleration time.
  • M
    margaretlynchAug 27, 2025
    What to do if Lenze DC Drives have a single phase fault?
    • A
      April MckeeAug 27, 2025
      If Lenze DC Drives have a single phase fault, it means a mains phase has been lost. Check the mains voltage.
  • N
    Natalie RamirezAug 28, 2025
    What to do if Lenze DC Drives have a communication error?
    • A
      athompsonAug 28, 2025
      If Lenze DC Drives have a communication error, it may be because the serial timer has timed out. Check the serial link connections.
  • S
    Scott WilliamsAug 29, 2025
    What to do if Lenze ESMD223L4TXA Inverter shows short-circuit or overload?
    • S
      Scott PhillipsAug 29, 2025
      If the Lenze Inverter experiences a short-circuit or overload, there are several potential causes: * A short-circuit itself: Investigate the cause and inspect the motor cable. * Excessive capacitive charging current: Use shorter motor cables. * Acceleration time is too short: Increase the acceleration time and check the controller selection. * Defective motor cable: Check the wiring. * Internal fault in the motor: Check the motor. * Frequent and long overload: Check controller selection.
  • J
    Jason ShawAug 29, 2025
    Why is my Lenze Inverter showing overvoltage on DC bus?
    • T
      Todd ArmstrongAug 29, 2025
      If your Lenze Inverter is experiencing an overvoltage on the DC bus, it could be due to several reasons: * The mains voltage might be too high: Verify the mains voltage. * The deceleration time might be excessively short, or the motor might be in generator mode: Increase the deceleration time or consider using a dynamic braking option. * Earth leakage on the motor side: Check the motor and motor cable, separating the motor from the controller to diagnose.
  • E
    Eileen BrooksAug 30, 2025
    What causes motor overload on Lenze ESMD223L4TXA Inverter?
    • W
      Whitney ThompsonAug 30, 2025
      If the Lenze Inverter displays a motor overload (I2t overload), it means the motor is thermally overloaded. This can be due to: * Impermissible continuous current. * Frequent or excessively long acceleration processes. To resolve this: * Check the controller selection. * Check the setting of c20.

Summary

Safety Information

General Safety Precautions

General safety warnings, risks of injury, and required qualifications for personnel.

Technical Data Overview

Product Ratings and Specifications

Detailed power, voltage, and current ratings for different models.

Installation Procedures

Electrical Installation and Wiring

EMC requirements, fuses, and cable cross-section recommendations.

Control Terminal Functions

Detailed description of each control terminal's function and settings.

Commissioning Guide

Troubleshooting and Fault Diagnosis

Error Codes and Solutions (cF-LF)

Detailed list of error codes, their causes, and corrective actions.

Error Codes and Solutions (OC1-SF)

Further error codes including short-circuit, earth fault, and overload.

Lenze ESMD223L4TXA Specifications

General IconGeneral
TypeInverter
Power Rating2.2 kW
Input Frequency50/60 Hz
Frequency0-500 Hz
Protection ClassIP20
Input Voltage380-480 V
Output Voltage0-480 V AC
Control Methodvector control
Communication InterfaceCANopen
Cooling MethodAir cooling