EasyManua.ls Logo

Lenze ESV251 1S Series - Page 42

Lenze ESV251 1S Series
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40 Lenze SMVector 13554876 EDBSV01 EN v21.0
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
p207
Proportional Gain 5.0 0.0 {%} 1000.0 Used to tune the PID loop:
Increase P207 until system becomes unstable,
then decrease P207 by 10-15%
Next, increase P208 until feedback matches
setpoint
If required, increase P209 to compensate for
sudden changes in feedback
p208
Integral Gain 0.0 0.0 {s} 20.0
p209
Derivative Gain 0.0 0.0 {s} 20.0
NOTE
Derivative Gain is very sensitive to noise on the feedback signal. Use with care.
Derivative Gain is not normally required in pump and fan applications
p210
PID Setpoint Ramp 20.0 0.0 {s} 100.0 time of setpoint change from P204 to P205
or vice versa.
Used to smooth the transition from one PID
setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)
p214
Minimum Alarm 0.0 P204 P205 Use with P140, P142 = 18...23
P215
Maximum Alarm 0.0 P204 P205
P231
Preset PID Setpoint #1 0.0 P204 P205 TB-13A activated; P121 = 3 and P200 = 1 or 2
P232
Preset PID Setpoint #2 0.0 P204 P205 TB-13B activated; P122 = 3 and P200 = 1 or 2
P233
Preset PID Setpoint #3 0.0 P204 P205 TB-13C activated; P123 = 3 and P200 = 1 or 2
P234
(2)
Preset PID Setpoint #4 0.0 P204 P205 TB-13D activated; P124 = 3 and P200 = 1 or 2
P240
Sleep Threshold 0.0 0.0 {Hz} 500.0 If drive speed < P240 for longer than P241,
output frequency = 0.0 Hz; drive display = SLP
P240 = 0.0: Sleep mode is disabled.
P200 = 0…2: Drive will start again when speed
command is above P240
P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242 or when the PID loop
requires a speed above P240.
P241
Sleep Delay 30.0 0.0 {s} 300.0
P242
Sleep Bandwidth 0.0 0.0 B
max
Where: B
max
= |(P205 - P204)|
P243
Feedback Sleep
Entry Threshold
0.0 P204 P205 Active only when P244 = 1 or 2
P244
Sleep Entry Mode 0 0 Enter SLEEP if Drive Speed <P240 For time longer than P241
1 Enter SLEEP if Feedback >P243 For time longer than P241 or same as Sel 0
2 Enter SLEEP if Feedback <P243 For time longer than P241 or same as Sel 0
P245
Sleep Entry Stop
Type
0 0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
P246
Feedback Recovery
from Sleep Threshold
0.0 P204 P205 Active only when P247 = 1 or 2
P247
Sleep Recovery
Mode
0 0 Recovery if Speed Setpoint > P240
or if PID feedback differs from setpoint
by more than P242
1 Recovery only if Feedback < P246
2 Recovery only if Feedback > P246
(2) Parameter applicable to SMV models 15HP (11kW) and higher.

Table of Contents

Related product manuals