Lenze SMVector 13554876 EDBSV01 EN v21.0 65
Code Possible Settings
IMPORTANT
No. Name Default Selection
P 300
Operating Mode 0
0 Constant V/Hz Constant torque V/Hz, for general applications
1
Variable V/Hz Variable torque V/Hz, for centrifugal fan and pump
applications
2
Enhanced Constant V/Hz - For single or multiple motor applications
that require better performance than settings 0 or 1 but cannot use
vector mode as no motor data is available or vector mode causing
motor instability
3 Enhanced Variable V/Hz
4
Vector Speed Single motor applications requiring high starting torque
and speed regulation
5
Vector Torque Single motor applications requiring torque control
independent of speed
Code Possible Settings
IMPORTANT
No. Name Default Selection
P 302
Motor rated voltage
P 303
Motor rated current
P 304
Motor rated frequency
P 305
Motor rated speed
P 306
Motor Cosine Phi
NOTE: Set P399 to 1 and provide a start command (see “start control source” above) to start the motor
auto-calibration. The display will show “CAL” for up to 40 seconds and then “STOP” once completed.
Vector Speed and Torque Control set-up (P300 = 4 or 5)
In Volts per Hz mode the drive linearly increases output voltage as a direct function of the drive’s output frequency by the
slopeofthelinedenedbyP165(basevoltage)andP167(basefrequency).Invectormodethedrivedevelopsamathematic
model of the motor to determine the phase angle of the stator current components to more accurately regulate speed for
dynamic applications and to provide a method for torque control.
NOTE: If P300 = 4 or 5, a motor auto-calibration must be carried out. Ensure motor nameplate
dataisprogrammedrst(detailedbelow).FailuretodosowillresultinaF.nldfaultmessage.